Sleipner PHC-3 Скачать руководство пользователя страница 5

 5

5267

15

2022

-

PHC-3

Menu

MC_0201

Alarm Bell

       (alarm bell) is flashing in upper left corner when any fault has been triggered. When a fault is triggered 

the display will jump to the FAULTS menu. Pushing the      (back) button will bring you back to the previous 

menu.

VFD

A symbol           power-pack AC motor is showing status of the VFD at the top. The fi eld will be blank when 

VFD is ready and not active. VFD must be confi gured in parameter 1001 for this symbol to show.

 

 

 

VFD is the active power source but motor is not running. 

         OFF    

VFD is not connected or not powered. 

 

 RUN    

VFD is running. 

 

 LOC    

VFD is in local mode. 

 

 ERR    

VFD is not ready or any fault. 

 

   

 

VFD is waiting for run enable signal from power management system.

OIL TEMP

Oil temp and oil level screen will not show if tank monitor sensor type parameter 0201 is deactivated.

Tank monitor sensor type set to analogue temp. 

Flashing text “COOLING” when cooling pump is running. 

Cooling starts at 45°C (113°F) and stops at 40°C (104°F).

Main Menu 

Use       arrow buttons to switch between these views:

1.2

1.2.1

1.2.2

1.2.3

1.2.4

1.2.5

1.

MAIN SCREENS and SYMBOLS

OIL LEVEL

Oil level is indicated with OK or LOW. 

If oil level sensor is analogue then oil level is also indicated with level in percent (i.e. 97%).

PRESSURE

Shows system pressure and power-pack pressure in bar.

Tank monitor sensor type set to NC temp (temp switch). 

Oil temp is indicated with NORMAL or HIGH. 

Flashing text “COOLING” when cooling pump is running.

ENTER/
SAVE

Page Up and 
Down
(Side to side)

Page BACK
/CANCEL

If no parameters are changed.

- If one or more parameters is changed.

- A list of all parameters that has been changed are viewed.

- The list can be scrolled by using the      arrow buttons.

- In the down right corner, you can see how many parameters that has been changed and 

in this example there are 5 changed parameters.

- Editing parameters cannot be done here.

- To restore all parameters to default values as setup from factory, push and hold the enter 

button for 3 seconds. When screen shows DEVICE INFO menu, parameters are restored.

Menu - Active Faults

Menu - Device INFO

MC_0201

MC_0201

FAULTS 

      flashing in upper left corner when any fault has been triggered. 

Go to ACTIVE FAULTS menu for fault details.

Menu - Active Faults 

      

Menu - Device INFO

      

Device INFO

CHANGED PARAMETERS

Indicates that there are no active faults. 

Each fault is shown with a fault code number (i.e. 10501.0.16) followed by code name (OIL TEMP) and at 

the second line a fault condition (SHORT CIRCUIT). 

PHC-3 serial number and fi rmware version.

Enter to see changed parameters. 

The PHC-3 controller parameters are setup specifi cally for each system at the factory. 

Changed parameters are parameters that do not match setup from factory.

Pressing   

ENTER will reset all faults. 

See separate document for Fault Code Descriptions.

2.

2.1

3.

3.1

3.1.1

Содержание PHC-3

Страница 1: ...d Norway www sleipnergroup com DOCUMENT ID REVISION DATE LANGUAGE To download your language go to www sleipnergroup com Including Installation For Hydraulic Proportional Controller PHC 3 5267 15 K e e...

Страница 2: ...Menu Parameters 6 12 Menu Diagnostic 13 16 Menu Operation 17 18 PHC 3 Alarm Descriptions 19 21 Installation Manual Responsibility of the Installer 22 Considerations and Precautions for S Link Systems...

Страница 3: ...display and button interface allow for local con guration of parameters and info LED Status Hydraulic cooling pump output Stabilizer hydraulics connections dump unload PTO main valve Power 24V Power...

Страница 4: ...or run enable signal from power management system OIL TEMP Oil temp and oil level screen will not show if tank monitor sensor type parameter 0201 is deactivated Tank monitor sensor type set to analogu...

Страница 5: ...ive Faults Menu Device INFO MC_0201 MC_0201 FAULTS flashing in upper left corner when any fault has been triggered Go to ACTIVE FAULTS menu for fault details Menu Active Faults Menu Device INFO Device...

Страница 6: ...ad sharing between two PTO pumps by shutting down the second PTO pump PUMP2 OUTPUT when not needed two PTO pumps control valves required to reduce heat generation in the system and save fuel energy Wh...

Страница 7: ...nalog temp sensor NTC 10K part no 10 2543 0202 OIL ALARM LEVEL Sets the oil alarm level 0 100 default 65 Alarm level in steps of 5 0203 TANK HEIGHT The height of the oil tank If tank don t have flat b...

Страница 8: ...PUMP TYPE 800rpm 1600rpm default 1400rpm Speed in steps of 100rpm 0304 POWER SAVE Cooling pump power save function DEACTIVATED POWER SAVE is deactivated and cooling pump will act accordingly to PUMP M...

Страница 9: ...ning 5 5 STERN THRUST ACTIVE Output is activated when stern thruster is running 6 6 ANY THRUST ACTIVE Output is activated when bow or stern thruster is running 7 7 THRUSTER ENABLED Output is activated...

Страница 10: ...nputs is active and all inputs must be deactivated to deactivate the function 0 NOT IN USE default Digital input is not in use and deactivated 1 1 START POWERPACK When the input is activated the AC po...

Страница 11: ...steps of 1 1009 PTO PUMP PRESSURE DETECT LEVEL De nes detection level for PTO standby pressure if parameter 0104 SYSTEM PRESSURE is set to ANALOG INPUT Pressure above level indicates that main engine...

Страница 12: ...he BOW valve output direction for all parameter 0102 THRUSTER CONFIG settings NORMAL default Normal thruster direction SWAPPED Swapped thruster direction 2003 MAX SPOOL TRAVEL Scaling of valves spool...

Страница 13: ...00ms default 200ms In steps of 100ms 2105 RAMP DECREASE De nes the time the output signal uses to go from 100 to 0 100ms 10000ms default 200ms In steps of 100ms 2106 DIRECTION LOCK De nes the time fro...

Страница 14: ...Pressure 4 Set MAX SPOOL TRAVEL parameter 2003 to what Output in shows at maximum thrust and maximum Sys Pressure Shows live update of inputs and outputs related to stern thruster function In Display...

Страница 15: ...0 Volt 1 output is energized When an output is highlighted the output will be toggled as long as the Enter button is being pushed and held In Display Description LS Dump LS Dump Valve Pump 2 Shutdown...

Страница 16: ...A 0bar STAB PRESSURE Stabilizer Pressure in mA 4 0mA 0bar Shows live update of digital inputs 0 input is shorted to 0 Volt activated 1 input is open deactivated Scroll down to view more inputs In Disp...

Страница 17: ...during reception increments the value After every successful reception the value is decremented Tx Error Count Transmit error counter Error during transmit increments the value After every successful...

Страница 18: ...is displayed While VFD is running it is possible to press Back and go to parameters and change parameter values like 1003 PRESSURE SETPOINT or view DIGITAL OUTPUTS Waiting for power management system...

Страница 19: ...DC current 3 1A ECI cooling pump motor peak current 12 4A Hydraulic cooling pump is selected in parameter 0301 and is ready to be operated The following data is shown in this example Hydraulic oil tem...

Страница 20: ...ircuit System pressure sensor open circuit Sensor not connected or wire break Verify system pressure parameter 0104 10503 0 16 PHC System Pressure Short Circuit System pressure sensor short circuit Wi...

Страница 21: ...ECI cooling pump overvoltage voltage higher than 33 0V Check PHC 3 input voltage is below 33 0V Replace ECI cooling pump 10524 0 54 PHC ECI Cooling Pump Undervoltage ECI cooling pump under voltage vo...

Страница 22: ...MC_0105 The installer must read this document to ensure necessary familiarity with the product before installation Instructions in this document cannot be guaranteed to comply with all international a...

Страница 23: ...system and attach using 4 M5x16 screws 2 Attach the required cables to the PHC 3 MC_0431 MG_0485 1 2 Tank sensor cable Black X3 S Link cable X5 Power colling pump cable Blue X1 Hydraulic colling pump...

Страница 24: ...esigned by olekr Copyright All rights reserved SLEIPNER MOTO 120 217 56 Supply Voltage 9 31 VDC Power consumption Less than 1 0 Watt in stand by Digital output 1 to 6 Max load 2 0 Amp pr output Digita...

Страница 25: ...eally be connected around the middle of the BACKBONE Cable to ensure an equal voltage drop at each end of the BACKBONE Cable The yellow and black wire in the POWER Cable shall be connected to GND and...

Страница 26: ...STB SCU GW 1 Panel TP 43A S link Encoder Encoder 1 4 2 SCU Power Supply cable 3 Encoder cable 5 Encoder cable 5 FCU Harness 6 FCU Harness 6 SCU FCU cable 7 SCU FCU cable 7 VFD BUS cable 8 Pump Power...

Страница 27: ...C 3 X1 Harness Part 151470 1 10 Pump power cable Part 10 2371 24v Pump power cable Part 10 2357 hyd MC_0218 IMPORTANT If installing S link products DO NOT connect any other control equipment to the S...

Страница 28: ...rial number ie Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure e...

Страница 29: ...to the Purchaser at the Warrantor s expense If on the other hand the claim is determined to result from circumstances such as described in section 4 above or a result of wear and tear exceeding that...

Страница 30: ...30 5267 15 2022 PHC 3 MC_0037 Notes...

Страница 31: ...31 5267 15 2022 PHC 3 MC_0037 Notes...

Страница 32: ...accuracies or omissions it may contain Continuous product improvement may change the product speci cations without notice Therefore Sleipner Group cannot accept liability for any possible differences...

Отзывы: