CANopen Agile
95
06/2010
Frequency Inverter Control
10.3.2
Behavior in Transition 5 (Disable Operation)
392 state-transition 5
The behavior in transition 5 (from "Operation released" to "Switched On") can set via parameter
state-
tr
ansition 5
392.
Parameter
Setting
No.
Description
Min.
Max.
Factory Setting
392 state-transition 5
0
2
2
Operation Mode
Function
0 - Coast to Stop
Immediate transition from "Operation released" to "Switched On", drive
coasts to a standstill.
1 - DC-Brake
Activation of DC brake, at the end of DC deceleration, there is the change
from "Operation released" to "Switched On".
2 - Ramp
Transition at normal ramp, when the drive has come to a standstill, there
is the change from "Operation released" to "Switched On".
Note:
Setting operation mode "1 - DC brake" is only possible in applications with v/f characteristic (e.g. configu-
ration 110), as other applications do not know such an operation mode.
If the frequency inverter is operated with a configuration which does not know the DC braking operation
mode (e.g. configuration 210, field-orientation speed controlled), value "1" cannot be set. It is also not
offered in the selection menus of the Operator Panel or the VPlus PC-Software.
Note:
The default value for parameter
State transition 5
392 is operation mode "2 - Ramp". For configurations
with torque control, the default value is operation mode "0 - Coast to stop".
If the configuration is changed, the value set for
State transition 5
392 is also altered, if necessary.
If transition 5 has been triggered with
State transition 5
392 = "1 - DC brake", a new control word is only
accepted after the completion of the transition process. The change of state from "Operation enabled" to
"Ready" is carried out after the time parameterized for the DC brake
Braking time
632 has expired.
If the parameter
State transition 5
392 = "2 - Ramp" has been set, the
controlword can be set back to
"Enable operation" during the stoppage of the drive. In this way, the drive runs back up to its set refer-
ence value and remains in the state "Operation enabled".
The change of state from "Operation enabled" to "Switched On" is carried out after the set switch-off thre-
shold has been reached and the set holding time (equivalent to the behavior in a quick stop) has expired.
In this, the Parameters
Switch-off Threshold Stop Function
637 (Percentage value of Parameter
Maxi-
mum Frequency
419) and
Holding Time Stop Function
638 (holding time after switch-off threshold
reached) are relevant.
Frequency Inverter Control
10.3.3
Reference Value / Actual Value
The PLC gives its reference value to the frequency inverter via Object
0x6042/0 Target Velocity
in the
RxPDO used and receives the information on its actual value back via Object
0x6044/0 Control effort
(current Speed) in the TxPDO used.
The use of the reference/actual value channel depends on the set configuration (control system). The
actual value is generated from the appropriate source depending on the control system used.
The reference value from Object 0x6042
Target-velocity is provided by the Fieldbus Reference Value.
In the Frequency Reference Value Channel the setting "20 – Fieldbus Reference Value" can be se-
lected via Parameter
Reference Frequency Source 1
475 or
Reference Frequency Source 2
492.
Actual Values
Parameter
Content
Format
Internal reference frequency
228 Sum of reference values
Reference Frequency Value Source 1
475 and
Reference Frequency Value Source 2
492.
xxx.xx Hz
Reference bus frequency
282 Fieldbus Reference Value from CANopen
®
bus
xxx.xx Hz
Reference ramp frequency
283 Current Reference Frequency of the Ramp
xxx.xx Hz
10.3.4
Example Sequence
One of the following sequences can be used:
1
Control Word =
0x0000
Disable Voltage
2 Control Word =
0x0006
Shutdown
3 Control Word =
0x0007
Switch On
4 Control Word =
0x000F
Enable Operation
OR
1
Control Word =
0x0000
Disable Voltage
2
Control Word =
0x000F
Enable Operation