CANopen Agile
39
06/2010
Objects
9.2
Communication Objects (0x1nnn)
The communication objects 0x1nnn contain all parameters for the communication.
Note: For easier use, the objects are summarized by a table in each paragraph. This table is addition-
ally marked by color.
Orange
= Read Only object
Green
= Read and Write object
Blue
= Write only object
Used Abbreviations:
Access:
r/w:
ro:
wo:
Map:
Def.-Val:
Access type
Read/Write
Read only
Write only
Mapping
Default value
The Examples show some typical data telegrams, which could be observed or used with a CAN analyz-
ing tool. The order displayed in the examples is the standard CANopen
®
format, lowest byte left, high-
est byte right.
Note: The headings are displayed in the format
Index/Subindex Objectname.
9.2.1 0x1000/0 Device Type
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x1000
0
Device Type
Unsigned 32
ro
No
0
The device identification is carried out during the start of the network. The information on the de-
vice type and the functionality (type) are prescribed by the CANopen
®
standards.
Object 0x1000/0
Additional Information
Device Profile Number
Mode Bits
Type
31
24 23
16 15
0
The "Drives and Motion Control" standard device profile used by the frequency inverter is portrayed
as device profile number 402. The additional information specifies the device functionality of the
frequency inverter.
Device Profile Number
= 402
drives and motion control
Type
= 1
frequency converter
Type
= 2
servo drive
Mode bits
= 0
unused
Example:
COB ID
CB
Index
SI
Data
Read Request
601
40
00 10
00
00 00 00 00
Response
581
43
00 10
00
92 01 41 00
CB: Control byte SI: Sub-Index All values in hexadecimal without leading "0x"
Objects
9.2.2 0x1001/0 Error Register
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x1001
0
Error Register
Unsigned 8
ro
No
0
Object 0x1001/0 is the error register for internal errors of the frequency inverter. The status error-
free (0x1001/0 = 0) or error exists (0x1001/0
≠
0) is displayed.
Object 0x1001/0
7
6
5
4
3
2
1
0
Bit
0
General error
1
Current
2
Voltage
3
Temperature
4
Communication error
5
Device profile-dependent error
6
Reserved
7
Manufacturer-dependent error
Example:
COB ID
CB
Index
SI Data
Read Request
601
40
01 10
00
00 00 00 00
Response
581
4F
01 10
00
00 01 41 00
CB: Control byte SI: Sub-Index