CANopen Agile
06/2010
82
Objects
9.5.12
0x6060/0 Modes of operation
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x6060
0
Modes of operation
Integer8
wo
Rx
2
Object
modes of operation is set fixed to "2 - velocity mode".
Modes of operation
2 – velocity mode
Refer to Chapter 10 "Frequency Inverter Control" for further information.
Example:
COB ID CB
Index
SI Data
Write Access
601
2F
60 60
00
02
Response
581
60
60 60
00
00
CB: Control byte SI: Sub-Index All values in hexadecimal without leading "0x"
9.5.13
0x6061/0 Modes of operation display
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x6061
0
Modes of operation display
Integer8
ro
Tx
2
Object
Modes of operation display acknowledges the fixed value set with
0x6060/0 Modes of opera-
tion
by displaying Operation Mode as the set fixed value of 2.
Note:
After setting
modes of operation, the PLC must wait for this acknowledgement before sending any
other command to the inverter.
For further information refer to Chapter 10 "Frequency Inverter Control".
Example:
COB ID CB
Index
SI
Data
Read Request
601
40
61 60
00
00
Response
581
4F
61 60
00
02
CB: Control byte SI: Sub-Index All values in hexadecimal without leading "0x"