CANopen Agile
43
06/2010
Objects
Example:
COB ID CB
Index
SI
Data
Read Request
601
40
07 10
00
00 00 00 00
Response
581
43
07 10
00
00 00 00 00
Write Access
601
23
07 10
00
D0 07 00 00
Response
581
60
07 10
00
00 00 00 00
CB: Control byte SI: Sub-Index All values in hexadecimal without leading "0x"
9.2.6 0x1008/0 Manufacturer Device Name
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x1008
0
Manufacturer Device name
Visible string
ro
No
See Text
The device version is displayed as a sequence of ASCII characters.
Example: "AGILE"
Object 0x1008/0 supports the segmented SDO transfer.
9.2.7 0x1009/0 Manufacturer Hardware Version
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x1009
0
Manufacturer Hardware version Visible string
ro
No
See Text
The hardware version is displayed as a sequence of ASCII characters.
Example: "AGL 400 512 344"
Object 0x1009/0 supports the segmented SDO transfer.
9.2.8 0x100A/0 Manufacturer Software Version
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x100A
0
Manufacturer Software version Visible string
ro
No
See Text
The software version is displayed as a sequence of ASCII characters.
Example: "5.1.2"
Object 0x100A/0 supports the segmented SDO transfer.
Objects
9.2.9 0x100C/0 Guard Time
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x100C
0
Guard time
Unsigned 16
r/w
No
0
The response monitoring time is calculated by the multiplication of the objects g
uard time and lifetime
factor. Object 0x100C/0 defines the guard time in units of one millisecond. Guard time = 0 deacti-
vates the guarding function. If the response monitoring time is exceeded, the node reacts as defined
by the setting of object
0x6007/0 Abort Connection option code
.
Example:
COB ID CB
Index
SI Data
Read Request
601
40
0C 10
00
00 00
Response
581
4B
0C 10
00
00 00
Write Access
601
2B 0C 10
00
D0 07
Response
581
60
0C 10
00
00 00
CB: Control byte SI: Sub-Index All values in hexadecimal without leading "0x"
9.2.10
0x100D/0 Lifetime Factor
Index Sub-Index
Meaning
Data Type Access Map Def.-Val
0x100D
0
Lifetime factor
Unsigned 8
r/w
No
0
The object "Lifetime Factor" is the multiplier for
guard time. Lifetime factor = 0 deactivates the guard-
ing function.
Example:
COB ID CB
Index
SI
Data
Read Request
601
40
0D 10
00
00
Response
581
4F
0D 10
00
00
Write Access
601
2F
0D 10
00
05
Response
581
60
0D 10
00
00
CB: Control byte SI: Sub-Index All values in hexadecimal without leading "0x"