Set-up via the Communication Interface
Parameter-setting and commissioning of the frequency inverter via one of the op-
tional communication interfaces include the plausibility check and the parameter
identification functions. The parameters can be adjusted by qualified users. The pa-
rameter selection during the guided commissioning procedure includes the basic pa-
rameters. These are based on standard applications of the corresponding configura-
tion and are therefore useful for commissioning.
Caution! Parameter settings may only be changed by qualified staff. Before start-
ing the commissioning process, read the documentation carefully and
comply with the safety instructions.
The parameter
SETUP Selection
796 defines the function which is carried out direct-
ly after the selection (if controller enabling signal is present at digital inputs
S1IND/STOA and S7IND/STOB). The operation modes include functions which are
also carried out automatically one after the other during the guided commissioning
procedure.
SETUP Selection
796
Function
0 - Clear Status
The auto set-up routine does not perform a func-
tion.
1 - Continue
The warning message is acknowledged and the
auto set-up routine is continued.
2 - Abort
The auto set-up routine is stopped and a RESET of
the frequency inverter is performed.
10 - Complete Setup, DS0
The auto set-up routine is performed in data set 0
and the parameter values are stored in all of the
four data sets identically.
11 - Auto set-up complete,
DS1
The parameter values of the auto set-up are stored
in data set 1.
12 - Auto set-up complete,
DS2
The parameter values of the auto set-up are stored
in data set 2.
13 - Auto set-up complete,
DS3
The parameter values of the auto set-up are stored
in data set 3.
14 - Auto set-up complete,
DS4
The parameter values of the auto set-up are stored
in data set 4.
20 - Check Machine Data, DS0 The auto set-up routine checks the rated motor
parameters in the four data sets.
21 - Plaus. contr. motor data,
DS1
The rated motor parameters in data set 1 are
checked for plausibility.
22 - Plaus. contr. motor data,
DS2
The rated motor parameters in data set 2 are
checked for plausibility.
23 - Plaus. contr. motor data,
DS3
The rated motor parameters in data set 3 are
checked for plausibility.
24 - Plaus. contr. motor data,
DS4
The rated motor parameters in data set 4 are
checked for plausibility.
30 - Calculation and Para-
Ident., DS0
The auto set-up routine determines extended mo-
tor data via the parameter identification feature,
calculates dependent parameters and stores the
parameter values in all of the four data sets identi-
cally.
31 - Calc. and para ident., DS1
Further motor data are measured, dependent pa-
rameters are calculated and the parameter values
are saved in data set 1.
32 - Calc. and para ident., DS2
Further motor data are measured, dependent pa-
rameters are calculated and the parameter values
are saved in data set 2.