Operating Instructions ACU
45
5.5
Connection of types
5.5.1 ACU 201 (up to 3.0 kW) and 401 (up to 4.0 kW)
The mains connection of the frequency inverter is via plug-in terminal X1. The con-
nection of motor and brake resistor to the frequency inverter is done via plug-in ter-
minal X2. Degree of protection IP20 (EN60529) is only guaranteed with the terminals
plugged.
Danger!
Switch off power supply before connecting or disconnecting the
keyed plug-in terminals X1 and X2. Dangerous voltage may be present
at the mains terminals and the DC terminals even after the frequency
inverter has been disconnected safely from power supply. Wait for some
minutes until the DC link capacitors have discharged before starting the
work.
•
The unit may only be connected with the power supply switched off.
•
Make sure that the frequency inverter is discharged.
Mains connection ACU 201 (up to 3.0 kW) and 401 (up to 4.0 kW)
X1
1ph / 230V AC
+
-
L1
L2 L3
L1
N PE
3ph / 230V AC
3ph / 400V AC
+
-
L1
L2 L3
L1
L2 L3 PE
2ph / 230V AC
+
-
L1
L2 PE
L2 L3
L1
250 W ... 1.1 kW
Phoenix ZEC 1,5/ .. ST7,5
0.2 ... 1.5 mm
AWG 24 ... 16
2
0.2 ... 1.5 mm
AWG 24 ... 16
2
0.25 ... 1.5 mm
AWG 22 ... 16
2
0.25 ... 1.5 mm
AWG 22 ... 16
2
2ph / 230V AC
1ph / 230V AC
1.5 kW ... 3.0 kW
L1
N
PE
+
-
L1 L2 L3
L1
3ph / 230V AC
3ph / 400V AC
PE
1.5 kW ... 3.0 kW
1.5 kW ... 4.0 kW
+
-
L1 L2 L3
L1
L1
L2
PE
L1
+
-
L1 L2 L3
L1
L2 L3
1
With a mains current above 10 A, the mains power connection 230 V 1ph/N/PE
and the mains power connection 230 V 2ph/N/PE are to be done on two termin-
als.