194
Operating Instructions ACU
09/08
Caution!
The default assignment of parameter
Start clockwise
68 to the logic
signal of the technology controller must be observed:
Start Clockwise
68 = 13 - Technology Controller Start.
This assignment may not be changed. The technology controller be-
comes active with the controller release at digital input S1IND/STOA.
Structural image: Inputs for reference percentage source
+
0
1
F3
analog
digital
MFI1
0
1
MFI1A
Multifunctional Input
Operation mode
452
Repetition Frequency
Input
Operation mode
496
Devider
497
S2IND
S3IND
S6IND
0
%
f
Technology Controller
Actual Percentage Source
478
Istwerte:
Actual Percentage Value
230
The function selected via the parameter
Operation mode
440
defines the behavior of
the technology controller.
Operation mode
440
Function
0 - off
The technology controller is switched off, the refer-
ence value specification is done via the reference
percentage channel.
1 - Standard
For pressure and volume flow control with linear op-
erating behavior and actual value monitoring.
2 - Liquid Level 1
Contents level control at defined motor speed with
actual value missing.
3 - Liquid Level 2
Contents level control at defined motor speed with
actual value missing or high control deviation.
4 - Speed Controller
Speed control with analog feedback of the actual
speed.
5 - Indirect Volume Flow
Control
Volume flow control with square rooted actual value.
Operating Instructions ACU
09/08
194