Open and close the ventilation system twice.
Adjust alle the inlets to be fully open at fully open
ventilation system.
Close the ventilation system. Check that the inlets
can close (5% slack on the winch motor).
Adjust all the inlets accordingly.
Differentiation:
Depending on the differentiation degree on the
inlets with delayed opening, place the cord in the
middle or lower line guide. Remember to place
the cord on the inner roller (the long roller).
The ventilation system is opened until the first
inlets reach an open position of 85mm. The
delayed inlets are now approx 25mm open.