25
SKF LAGD 1000
Designation
Number of outlets
Running time (tCo) for one
internal cycle of progressive
feeder giving 0,2 cm
3
/outlet
(minutes)
LAGD 1000/DC10
10
1,0
LAGD 1000/DC12
12
1,2
LAGD 1000/DC14
14
1,4
LAGD 1000/DC16
16
1,6
LAGD 1000/DC18
18
1,8
LAGD 1000/DC20
20
2,0
Using the calculated example shown in section 3. If the LAGD 1000/DC10 was to be used,
then the contact time (tCO) should be set to 1,0 minutes (meaning that all outlets receive
0,2 cm
3
). The tPA should be set to 4,4 hours.
4.3.2 Programming sequence LAGD 1000/AC.. and LAGD 1000/DC
The table below shows the sequence of how to program the unit.
Step
Key
Display
1
Press for more
than 2s
000 in display lashes
2
Press briely
(conirm code)
Automatically indicates irst parameter
Example:
“Pause in timer operation”
LED “Pause” lashes
3
Press briely
Pause time 1 h (factory setting).
Values between 0,1 and 99,9 hrs,
should be a minimum of :
• LAGD 1000/AC 4 x pump running
time (tCO) in hours. eg. if tCO =
5 minutes, tPA=0,4 hours minimum
• LAGD 1000/DC 9x pump running
time (tCO) in hours. eg. if tCO =
5 minutes, tPA=0,8 hours minimum
Содержание LAGD 1000 series
Страница 1: ...SKF LAGD 1000 Instructions for use ...
Страница 10: ...10 SKF LAGD 1000 1 4 LAGD 1000 unit dimensions Fig 2 LAGD 1000 DC dimensions Fig 3 LAGD 1000 AC dimensions ...
Страница 33: ...33 SKF LAGD 1000 ...
Страница 34: ...34 SKF LAGD 1000 ...
Страница 35: ......
Страница 37: ...1 5 0 1 0 0 9 Appendix 1 LAGD 1000 series Mounting hole drilling template MP5234 Appendix ...