Never clean the heat exchanger with a damp cloth, as this could damage the unit or cause an electric
shock (in the case of the version with the electric heat exchanger XR1-xxx-ECE1...) after restarting the
unit.
7.1.2. Visual Inspection of the Supply Cable
-
Visually check that the supply cable is not damaged, loosen, or torn from the connecting peripherals.
-
In case of damage, consult with the person competent for this activity with the valid authorisation and
knowledge of the relevant standards and directives.
2. Inspection – cleaning of the inner area of the unit – disassembly
-
Pay increased attention to disassembly of the internal components of the unit. Improper disassembly
may cause the unit to malfunction or limit its functions.
-
Remove the front metal cover (position 1) – see Section 6.1. (1 and 2).
-
Remove the M6x25 bolts that hold the unit cover (position 5)
o
XR1-010-EC…
o
XR1-025-EC…
7 pc
9 pc
-
Slide out the unit cover (position 5)
REMOVE THE BOLTS
1
LIFT OFF THE UNIT COVER TO ACCESS
ITS INTERNAL COMPONENTS
2
Fig. 40
-
Subsequent sub-categories of the manual are successive operations to be followed in the indicated
sequence.
-
After removing the unit cover, the unit may be removed from the installation template (all the
installation bolts are removed). After the re-assembly, tighten the unit back to the installation
template.
7.2.1. Cleaning the Fan Chamber and Fans
-
Remove the filters (position 8).
-
Carefully slide the fan beam assembly (position 11) out of the groove in the unit body.
-
With utmost caution, rotate the assembly around the cable axis down and the beam towards the unit
body.
46
Version 1 – GBR(23/06/2021)
D-502-0152
Fig. 41