 7 

S4010-0001-14 

 

6/2014

Input Power Requirements 

Voltage Range 

Frequency 

Maximum Current 

AC Input, 120 VAC base models 

102 to 132 VAC 

60 Hz 

2 A  

AC Input, 240 VAC base models 

204 to 264 VAC 

50/60 Hz 

1 A 

AC Input with 120 VAC expansion power supply 

102 to 132 VAC 

60 Hz 

4 A 

AC Input with 240 VAC expansion power supply 

204 to 264 VAC 

50/60 Hz 

2 A 

Environmental

 

Operating Temperature Range 

32° to 120°F (0° to 49° C) 

Operating Humidity Range 

up to 93% RH, non-condensing @ 100.4° F (38° C) maximum 

Output Ratings 

Standard Power Supply Output 

Rated 4 A for “Special Application” appliances and for 
“Regulated 24 DC” appliance power; Battery charger for up to 25 Ah 
sealed lead-acid batteries 

Notification Appliance Reference 

Special Application 

Simplex 4901, 4903, 4904, and 4906 Series horns, strobes, and 
combination horn/strobes and speaker/strobes (contact your Simplex 
product representative for compatible appliances) 

Regulated 24 DC 

Power for other UL listed appliances; use associated external 
synchronization modules where required 

Auxiliary Power Output Tap from Standard Power 
Supply 

Rated 0.5 A maximum @ 19.4 to 32 VDC; 
subtract current used from standard power supply output 

Expansion Power Supply Output 

Rated 4 A for “Special Application” appliances and auxiliary power;  
Rated 2 A for “Regulated 24 DC” appliance power; 
Two output taps of 2 A each are provided 

NAC Ratings 

2 A each maximum; up to 33 synchronized strobes maximum per NAC 

Current Ratings for Optional Modules and Remote LCD Annunciator 

Model 

Module 

Supervisory  

Current

 

Alarm  

Current 

4010-9810 

DACT (Common Event Reporting) 

40 mA 

40 mA 

4010-9816 

DACT (Point Reporting) 

40 mA 

40 mA 

4010-9821 

Network, wired communications 

125 mA 

125 mA 

4010-9817 

Network Modular, add media cards separately 

24 mA 

24 mA 

4010-9818 

Network Wired Media  

47 mA 

47 mA 

4010-9819 

Network Fiber Optic Media  

36 mA 

36 mA 

4010-9811 

Dual RS-232  

75 mA 

75 mA 

4010-9812 

Single RS-232 with Service Modem 

100 mA 

100 mA 

4010-9806 

Dual Class A NAC Adapter 

0 mA 

0 mA 

4010-9809 

Dual Circuit City Connect 

20 mA 

36 mA 

4010-9829 

Dual Circuit City Connect w/o disconnect switches 

20 mA 

36 mA 

4010-9803 

Relay Option Module 

10 mA 

37 mA 

4010-9860 
4010-9861 

& ULC 4010s 

24 LED Annunciator door  

60 mA 

83 mA 

(all LEDs on) 

4606-9101 

Remote LCD Annunciator (refer to data sheet S4606-0001) 

65 mA 

140 mA 

System Current (supplied separate from power supply output) 

Base System with: 

Supervisory 

Current**

 

Alarm  

Current** 

 

no IDNet devices 

195 mA 

295 mA 

 

50 IDNet devices 

230 mA 

330 mA 

 

100 IDNet devices 

265 mA 

365 mA 

 

150 IDNet devices 

300 mA 

400 mA 

 

200 IDNet devices 

335 mA 

435 mA 

 

250 IDNet devices 

370 mA 

470 mA 

** Current Calculation Information: 

1.  To determine total supervisory current, add currents of modules in panel to base system value 

and

 all auxiliary loads. 

2.  To determine total alarm current, add currents of modules in panel to base system alarm current 

and

 add all panel NAC loads 

and

 all auxiliary loads. 

 4010 Operating Specifications 

Содержание TrueAlarm

Страница 1: ...with standard door Description TrueAlarm fire alarm control panels have the ability to provide location accuracy for monitoring and control When equipped with TrueAlarm analog sensing for smoke and he...

Страница 2: ...recognizable audible notification signal audible WALKTEST operation 2 S4010 0001 14 6 2014 SUPV ACK SYSTEM SUPERVISORY ALARM ACK FIRE ALARM TROUBLE ACK SYSTEM TROUBLE ALARM SILENCE ALARM SILENCED SYS...

Страница 3: ...ent levels of smoke obscuration in percent or for specific heat detection levels In order to evaluate whether the sensitivity should be revised the peak value is stored in memory and can be easily rea...

Страница 4: ...ENCED SYSTEM RES ET AC POWER Local maintenance computer One connection type per 4010 selected by module choice max wiring distance is 300 ft 91 m 9600 baud RS 232 Connection Options refer to module s...

Страница 5: ...ork Interface Modular Media Available for wired connections or fiber optic Require separate media modules May be both wired both fiber optic or one of each Optional Expansion Slot Modules Cont d Netwo...

Страница 6: ...liances rated 2 A for Regulated 24 DC appliance power 4010 9823 240 VAC input Optional Features select as indicated 4010 9825 24 VDC Expansion Power Distribution Module provides two additional termina...

Страница 7: ...each maximum up to 33 synchronized strobes maximum per NAC Current Ratings for Optional Modules and Remote LCD Annunciator Model Module Supervisory Current Alarm Current 4010 9810 DACT Common Event Re...

Страница 8: ...1 2 368 mm WATERFLOW LEFT WING GROUND FAULT WATERFLOW RIGHT WING SUPV ACK SYSTEM SUPER VISORY ALARM ACK FIR E ALARM TROU BLE ACK SYSTEM TROUBLE ALARM SILENCE ALARM SILENC ED SYSTEM RESET AC POWER MENU...

Отзывы: