TrueAlarm Information Details
True Alarm sensor data
can be displayed on the
system LCD, on a remote maintenance PC, or printed on a
remote printer. With the proper operator access, a
TrueAlarm Service Report can be generated to list the
specific details of each TrueAlarm device. This report, as
well as the Status Report can either be displayed on the
remote maintenance PC or captured permanently by using
a remote 80 character printer.
Status and Service Reports.
The report samples
below illustrate the format provided on either the remote
maintenance PC or a printer. This information is available
at the system LCD by identifying the specific point of
interest and reading one point at a time.
Compatible Printer.
Model 4190-9013 is a UL
Standard 864 listed 80 column, 24 pin dot matrix printer
(refer to data sheet S4190-0011).
4010 Fire Alarm
Control Panel
Printer (Simplex
model 4190-9013)
Remote authorized maintenance
computer connected via dial-up
Service Modem Connection
FIRE ALARM
CONTROL
D ISC ON NEC T
POWER BEFORE
SER VIC ING
CAUTION
** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
S UPV
ACK
SYSTEM
SUPERVISORY
ALARM
A CK
FIRE
ALARM
TROU BLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RES ET
AC
POWER
Local
maintenance
computer
One connection type per 4010,
selected by module choice; max.
wiring distance is 300 ft (91 m)
@ 9600 baud
RS-232 Connection Options
(refer to module selection on page 6)
4
S4010-0001-14
6/2014
Simplex 4010 Fire Alarm System
Page 1
REPORT 4 : TrueAlarm Service Report
2:56:09 pm Tue 10-Jun-14
Dev
Num
Custom Label
Alarm
at:
Avg
val
Current/
% alarm
Peak/
% alarm
State
1
ANALOG PHOTO - CLEAN ROOM
0.5/ 83
67
68/ 1%
72/ 10%
NOR
2
ANALOG ION - CLEAN ROOM
1.3/209
94
97/ 2%
101/ 1%
NOR
3
ANALOG PHOTO - MAIN LOBBY
2.5/185
117
117/ 0%
125/ 42%
NOR
4
ANALOG PHOTO - CONFERENCE ROOM 1
2.5/161
93
93/ 0%
93/ 0%
NOR
10
HEAT DETECTOR - GARAGE
135F/253
–--
63/-67F
66/ 69F
NOR
11
ANALOG PHOTO - KITCHEN
3.7/216
116
116/ 1%
110/ 36%
NOR
END OF REPORT
Typical TrueAlarm Service Report Information Printout and/or Maintenance PC Screen
Simplex 4010 Fire Alarm System
Page 1
REPORT 3 : TrueAlarm Status Report
2:43:03 pm Tue 10-Jun-14
Zone
Name
Custom Label
Sensi-
tivity
Device Status
Almost
Dirty
M1-1
ANALOG PHOTO
CLEAN ROOM
0.5 %
NORMAL
M1-2
ANALOG ION
CLEAN ROOM
1.3 %
NORMAL
M1-3
ANALOG PHOTO
MAIN LOBBY
2.5 %
NORMAL
*YES*
M1-4
ANALOG PHOTO
CONFERENCE ROOM 1
2.5 %
NORMAL
M1-10
HEAT DETECTOR
GARAGE
135 F
NORMAL
M1-11
ANALOG PHOTO
KITCHEN
3.7 %
NORMAL
*YES*
END OF REPORT
Typical TrueAlarm Status Report Information Printout and/or Maintenance PC Screen
TrueAlarm Status and Service Report Samples