background image

 

  

 6 

S4010-0001-14 

 

6/2014

Category 

Model

 

Description  

Voltage 

Color 

Control Panel 

Assembly

 

(select one)

 

4010-9101 

UL Listed 4010 Fire Alarm Control Panel

 with: door, cabinet, power 

supply/battery charger, IDNet interface, 4 NACs, 2 programmable 
auxiliary relays, and external N2 communications interface; 4010-9101 
and 4010-9102 include internal common event reporting DACT  

120 VAC 

Beige 

4010-9102 

Red 

4010-9201 

240 VAC 

Beige 

4010-9202 

Red 

4010-9101C English 

ULC Listed 4010 Fire Alarm Control Panel

; same as above 

except: with 24 LED Annunciator door; and without DACT 

120 VAC 

Beige 

4010-9101CF French 

 

4010-9150 UL 

Listed 

4010 Fire Alarm Control Panel, Electronics Only;

 for pre-shipped 

cabinets, requires door and cabinet ordered separately; 120 VAC input; 
4010-9150 has event reporting DACT; C & CF suffix models delete DACT 

4010-9150C 

ULC 
Listed 

English

4010-9150CF French 

Optional Expansion Slot Features

 

(two slots are available, select modules as required)

 

Category 

Model 

Description 

Reporting and 

Network Modules

 

(select one)

 

4010-9810 

DACT Module (Common Event Reporting) 

Includes two, 7 ft (2.1 m) long RJ45 cables 

4010-9816 

DACT Module (Point Reporting) 

4010-9821 

Network Interface Module with fixed, wired connections 

4010-9817 

Network Interface Module, Modular; requires 2 (In/Out) media modules (see below) 

Media Modules

 

4010-9818 

Network Wired Media Module 

Media modules mount on the 4010-9817 module 
without impact to slot allocation space. 

4010-9819 

Network Fiber Optic Media Module 

RS-232 

Communications 

(select one)

 

4010-9811 

Dual RS-232 Interface Module 

4010-9812 

Single RS-232 Interface Module with Service Modem connection 

Chassis Mounted Expansion Modules

 

(select as required)

 

Category 

Model 

Description  

Expansion Power 

Supply

  

(select one)

  

4010-9813 

120 VAC input 4 A Expansion Power Supply; rated 4 A for “Special Application” appliances; 

rated 2 A for “Regulated 24 DC” appliance power 

4010-9823 

240 VAC input

Optional Features 

(select as 
indicated)

 

4010-9825 

24 VDC Expansion Power Distribution Module, provides two additional termination points for 
an expansion power supply  tap or the auxiliary power output 

4010-9806 

Dual Circuit Class A NAC Adapter Module, 

two maximum

 

4010-9809 

Dual Circuit City Connect Module 

Select one maximum

 

4010-9829

*

 

Dual Circuit City Connect Module w/o disconnect switches 

4010-9803 

Relay Option Module 

Accessories

 

 

Category 

Model 

Description 

Optional Features

 

4010-9826 

120 VAC Auxiliary Relay Kit, allows 

one

 auxiliary relay to control up to 0.5 A @120 VAC, 

select as required; 

2 maximum

 

4010-9830 

(CAF) 

Suppression Release Appliqué, required for suppression release applications; suffix CAF 
selects a French appliqué 

2975-9801 

Semi-flush trim, beige, 1 

7

16

” (37 mm) wide 

2975-9802 

Semi-flush trim, red, 1 

7

16

” (37 mm) wide 

Batteries 

(required if 

batteries are 

internal; select one 

size; 

two batteries 

are required

)

 

2081-9272 

6.2 Ah Battery, 12 VDC 

2081-9274 

10.0 Ah Battery, 12 VDC 

2081-9288 

12.7 Ah Battery, 12 VDC 

2081-9275 

18 Ah Battery, 12 VDC; 

NOTE: This battery size will not allow bottom entry conduit

 

2081-9287 

25 Ah Battery, 12 VDC 

Cabinets

 (select 

one if pre-shipped)

 

2975-9215 Red 

Cabinet 

Dimensions: 22” H x 18” W x 5 

” D 

(559 mm x 457 mm x 137 mm) 

2975-9214(CF)  Beige Cabinet; CF suffix has French labels 

Doors 

(select one 

if pre-shipped or 

for use with 
4010-9150)

 

4010-9858 

Red Door with dress panel 

Dimensions: 22” H x 18” W x 

” D 

(559 mm x 457 mm x 16 mm) 

4010-9857(CF)  Beige Door with dress panel; CF has French labels 

4010-9860* 

Beige Door with 24 LED Annunciator and dress panel  Dimensions: 22” H x 18” W x 1 

23

32

”D 

(559 mm x 457 mm x 44 mm) [see 
also S4010-0002] 

4010-9861* 

Red Door with 24 LED Annunciator and dress panel 

*  

As of document revision date: 4010-9829 is not ULC listed;  

4010-9860 and 4010-9861 are listed by UL, ULC, and CSFM; and FM approved;  

 4010 Fire Alarm Control Selection Chart and Module Location Rules 

(refer to diagrams on page 8)

 

Содержание TrueAlarm

Страница 1: ...with standard door Description TrueAlarm fire alarm control panels have the ability to provide location accuracy for monitoring and control When equipped with TrueAlarm analog sensing for smoke and he...

Страница 2: ...recognizable audible notification signal audible WALKTEST operation 2 S4010 0001 14 6 2014 SUPV ACK SYSTEM SUPERVISORY ALARM ACK FIRE ALARM TROUBLE ACK SYSTEM TROUBLE ALARM SILENCE ALARM SILENCED SYS...

Страница 3: ...ent levels of smoke obscuration in percent or for specific heat detection levels In order to evaluate whether the sensitivity should be revised the peak value is stored in memory and can be easily rea...

Страница 4: ...ENCED SYSTEM RES ET AC POWER Local maintenance computer One connection type per 4010 selected by module choice max wiring distance is 300 ft 91 m 9600 baud RS 232 Connection Options refer to module s...

Страница 5: ...ork Interface Modular Media Available for wired connections or fiber optic Require separate media modules May be both wired both fiber optic or one of each Optional Expansion Slot Modules Cont d Netwo...

Страница 6: ...liances rated 2 A for Regulated 24 DC appliance power 4010 9823 240 VAC input Optional Features select as indicated 4010 9825 24 VDC Expansion Power Distribution Module provides two additional termina...

Страница 7: ...each maximum up to 33 synchronized strobes maximum per NAC Current Ratings for Optional Modules and Remote LCD Annunciator Model Module Supervisory Current Alarm Current 4010 9810 DACT Common Event Re...

Страница 8: ...1 2 368 mm WATERFLOW LEFT WING GROUND FAULT WATERFLOW RIGHT WING SUPV ACK SYSTEM SUPER VISORY ALARM ACK FIR E ALARM TROU BLE ACK SYSTEM TROUBLE ALARM SILENCE ALARM SILENC ED SYSTEM RESET AC POWER MENU...

Отзывы: