background image

Compact Auto FuelPort Operating Instructions - 

 8

Open Fill Valve

If 95% level is 

reached, 

audible and 

visual alarms 

are activated. 

The Compact 

Automatic 

Fuel Port 

valve closes 

completely 

and cannot 

be reopened 

until the level 

falls below 

95% level.

Calibrating the Meter: 

Once the tank is filled to a known quantity of  fuel, it may be necessary to 

calibrate the meter by changing the meters offset value.

Enter the setup menu as described above.  When the meter displays 

rANGE,

 press 

SEL

 twice until it displays 

OFSet

.  Press 

RST

 to change the 

setting to the value that will adjust the reading to match the amount of fuel 

in your tank.  If you need to enter a negative value, press 

SEL

 until the left-

most digit is flashing, then press 

RST

 until a negative sign appears.

When you have entered a value, press and hold 

SEL

 to return to the menu, 

then press 

SEL 

ten more times until 

NO 

is displayed.  The meter should 

exit the menu on it's own after about a second.

If the meter does not display the correct value, repeat the process to enter 

a new offset until the meter is accurate. 

III-

C. OPERATING INSTRUCTION

S

 

2.

Unlock the fill box.

3.

Connect the delivery hose to the coupling in the

 

CAFP.(See 

Control Power

)

4.

Open the valve on the truck.

5.

Turn the Control Power Switch on and press the 

Fill

 

Valve Open pushbutton.(See 

Open Fill Valve

 )

6.

The valve opens.

7.

Start the delivery pump on the truck.

8.

Fuel is delivered to the tank.

9.

The delivery may be stopped at anytime by 

pressing

 

the Close Fill Valve button and proceeding 

to step #13.

10.

At the 90%(typical) fuel level, audible and visual

 

alarms are activated and the valve will close partially 

to

 

restrict flow.

11.

Stop the delivery pump on the truck.

12.

Close the valve on the truck.

13.

Drain the delivery hose.

14.

Disconnect the delivery hose from the CAFP.

15.

Turn Control Power off.

16.

Close and Lock the Fill Box.

17.

Fuel Delivery is completed

18.

Disconnect the ground cable from the ground stud. 

1.

Connect the truck ground cable to the stud 

provided

 

on the CAFP. 

Control Power

Содержание Automatic Fuel Port

Страница 1: ...Automatic Fuel Port Full Size Fuelport Compact Fuelport Compact Automatic Fuelport Mini Smartpump Smartpump Enclosed Smartpump Tank Filling Systems TANK FILLING SYSTEM MANUAL Ship Loose Controller...

Страница 2: ...tion 6 III B Setting up the Meter 7 III C Operating Instructions 8 III D Maintenance Troubleshooting 9 III Compact Automatic FuelPort IV A Installation 10 IV B Setting 11 IV C Operating Instructions 1...

Страница 3: ...ly while standing on such insulative mats Never wear jewelry when working on this equipment Jewelry can conduct electricity resulting in electric shock or may get caught in moving components causing i...

Страница 4: ...ckets Follow all necessary safety procedures when welding the brackets to your tank Simplex is not responsible for damages or injuries sustained due to improper safety precautions Attaching FuelPort t...

Страница 5: ...pre drilled mounting flanges running the height and length of the cabinet Verify that the surface you are mounting the Full Sized FuelPort to and the mounting hardware are sufficient to support the F...

Страница 6: ...responsible for damages or injuries sustained due to improper safety precautions Attaching CAFP to Post With the post mounting option the CAFP can be attached to a free standing post See Post To do so...

Страница 7: ...which calibrates the meter for greater accuracy To enter the meter s setup menu press and hold the SEL button for one second The screen will begin alternating between Pro and NO Press RST while it sh...

Страница 8: ...t the menu on it s own after about a second If the meter does not display the correct value repeat the process to enter a new offset until the meter is accurate III C OPERATING INSTRUCTIONS 2 Unlock t...

Страница 9: ...capacity Check FuelPort piping for obstructions Checking drawing package to verify valve is wired correctly Verify controller is supplied with power Remove controller cover and verify relays are seate...

Страница 10: ...all control power see job specific wiring diagrams for details Installing Motorized Ball Valves If you have a single tank system the ball valve is likely already mechanically and electrically installe...

Страница 11: ...touch screen See Setup Menu Please refer to Appendix B for 7 inch touch screen examples System Setup If MBVs are installed you may enter the delay time in seconds for the valve fail timer You may also...

Страница 12: ...xt enter the tank interior depth height in inches in the Height field Enter the maximum tank capacity in gallons in the Gallons field See Tank Transducer You must also enter the transducer length at 2...

Страница 13: ...Refill Reminder Warning Should a tank reach this level a warning will be generated to inform the site personnel that a fuel delivery should be scheduled Entering 0 disables this feature See Low Fuel...

Страница 14: ...ow certain option to appear on the screen and powers the motorized ball valves Select the appropriate tank by pressing the level indicator for the required tank This will take you to the individual ta...

Страница 15: ...s for the selected tank will be prohibited See Tank High Another tank may be selected for fill if applicable Repeat the fill process for all tanks in the system Once filling is completed close any man...

Страница 16: ...on board pump Prohibits fill of selected tank Audio Visual Alarm Closes all valves Stops on board pump Prohibits fill of all tanks Audio Visual Alarm Closes all valves Stops on board pump Prohibits fi...

Страница 17: ...fuses are blown Tank indicates Full High and Critical High 1 Reconnect float stem 2 Check float stem wiring 3 Replace fuses 4 Cease filling operations 1 The float stem has been disconnected 2 The floa...

Страница 18: ...top Fill button on the touch screen or F2 if applicable 12 When the Tank Full level is reached an indication will be displayed the alarm horn will sound the fill valve will close and or the on board p...

Страница 19: ...on in finished equipment are not covered by this warranty g components or assemblies specified by buyer with no substitution permissible that are not normally used by SIMPLEX SIMPLEX reserves the righ...

Страница 20: ...7 Inch Screen Reference 20 APPENDIX B 7 INCH SCREEN REFERENCE Setup Modbus Settings Tank Setup Tank Type Tank Transducer 1 Tank Transducer 2 Startup Screen Zero Transducer...

Страница 21: ...7 Inch Screen Reference 21 Silence Horn Tank Select Tank Detail Screen Start Fill Tank Full Tank High Main Screen Alarm APPENDIX B 7 INCH SCREEN REFERENCE...

Страница 22: ...ill button b Turn off the control power circuit breaker c d e OpentheControlPanel door toaccessthe controlcompartment Locatetheoverloadrelay See OverloadRelay On either side of the relay reverse the b...

Страница 23: ...urge the pump of air on initial startup or whenever as has entered the pump system 1 Open the Smartpump inlet and outlet valve to flood the system See Pump Inlet Valve and Pump Outlet Valve 2 Open the...

Страница 24: ...your Load Bank and Fuel Supply needs Simplex Inc 5300 Rising Moon Road Springfield IL 62711 800 637 8603 www simplexdirect com This manual and all of its contents Copyright 2019 Simplex Inc All Right...

Отзывы: