Maintenance and Troubleshooting
-
9
Remove all
power before
servicing the
CAFP. Never
operate or
service a
CAFP that is
not grounded.
Problem
Controller
reporting
wrong fuel
level
Ball valve not
opening and/
or closing
correctly
Controller
not operating
Solution
Verify float assembly is wired correctl
y.
Verify float assembly is fully installed in tank receptacle. Adjust offset.
If your tank is rectangular, check setting for tank capacity.
Check FuelPort piping for obstructions.
Checking drawing package to verify valve is wired correctly.
Verify controller is supplied with power. Remove controller cover and
verify relays are seated securely.
Check tightness of electrical connections.
III-D. MAINTENANCE/TROUBLESHOOTING
General Maintenance:
All electrical connections should be tightened every 6
months.
Troubleshooting:
Although the Compact Automatic FuelPorts are
designed with trouble-free operation in mind, some
problem can arise. Please consult the following table
for solutions to the most common issues before
contacting a Simplex service representative.