User manual - WEIGHT METER SWI-94
Figure 4.15. Terminals description (OC-type and active voltage outputs)
Depending on version:
85...
230
...260V AC/DC or
19...
24
...50V DC; 16...
24
...35V AC
Figure 4.16. Connection of power supply and relays
Contacts of relay outputs are not equipped with spark suppressors. While
use the relay outputs for switching of inductive loads (coils, contactors,
power relays, electromagnets, motors etc.) it is required to use additional
suppression circuit (typically capacitor 47nF/ min. 250VAC in series with
100R/5W resistor), connected in parallel to relay terminals or (better) directly
on the load. In consequence of using the suppression circuit, the level of
generated electromagnetic disturbances is lower, and the life of relay
contacts rises.
15
!
FUSE
1
2
L N
L N
10 11 12 13
FUSE
R1
R2
1
2
5 6 7 8 9
30 31 32 33 34
10 11 12 13 14 15
3 4
35
+24V
+5%, -10%
I
max = 100mA
+
Uo
-
GND
RS - 485
DATA+
DATA-
programmable
input
(polarity
doesn't matter)
EXC+
SENSE+
SIGN+
SENSE-
SIGN-
EXC-
OC1 ÷ OC2:
U
max = 30V DC,
I
max = 30mA,
P
max = 100mW
(optional)
OC2
+ -
(optional)
OC1
- +
Power
supply
(depending on version)
-
+
ACTIVE
voltage output
(optional)
Содержание SWI-94
Страница 54: ...User manual WEIGHT METER SWI 94 54...
Страница 55: ...User manual WEIGHT METER SWI 94 55...