User manual - WEIGHT METER SWI-94
the procedure of the analogue outputs determining is
presented in details.
“
AL
”
- this parameter determines the behaviour of analogue output if any critical situation
occurs. According to version of the device, this parameter can be set:
For active current output:
“noCH”
- current will not change,
“22.1”
- current will be set to 22.1 mA,
“3.4”
- current will be set to 3.4 mA,
“0.0”
- current will be set to 0 mA.
For passive current output:
“noCH”
- current will not change,
“22.1”
- current will be set to 22.1 mA,
“3.4”
- current will be set to 3.4 mA,
For active voltage output:
“noCH”
- voltage will not change,
“11.0”
- voltage will be set to 11 V,
“5.5”
- voltage will be set to 5.5 V,
“1.2”
- voltage will be set to 1.2 V.
“0.6”
- voltage will be set to 0.6 V,
“0.0”
- voltage will be set to 0 V.
When the critical situation goes, the output signal will be set to value calculated due to
formulas given above.
If parameter
“OUtmod”
is set to “
oFF
”, “
4-20
”, “
0-20
”, “
0-5
”, “
1-5
”, “
0-10
” or “
2-10
” the “critical
situation” means that
nominal measurement range
is exceeded.
If parameter
“OUtmod”
is set to
“modbuS”
, the “critical situation” means communication
delay (when no data is received) longer than
“mbtimE”
parameter (see
Before turning off the device it is recommended to first disable the current
output's power supply, and then the device itself. If the current output is supplied
while the device itself is turned off, the output current will be about 27.5 mA.
7.3.5.
”button” menu
This menu allows enabling of functions realised by
[>0<]
,
[ T ]
and
[ B/N ]
buttons.
”b ZEro”
- enable of zeroing function - button
[>0<]
:
“oFF”
- disabled,
“on”
- enabled.
”b tArE”
-
enable of tare function - button
[ T ]
:
“oFF”
- disabled,
“on”
- enabled.