User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
The logical channels used for this example should be set as follows:
for
Logical channel 1
:
Name
: Temperature,
Mode
: Hardware input,
Source
: Inp. A1 (we assume that the built-in input is connected and set properly for
TC type K),
Precision
: 0,
Graph Lo
: 0,
Graph Hi
: 300,
all the other parameters should be on default settings,
for
Logical channel 2
:
Name
: Desired temp.,
Mode
: Set point value,
Unit
:
C,
Edit Button
: enabled,
Edit range low
: 120,
Edit range high
: 200,
Precision
: 0,
Graph Lo
: 0,
Graph Hi
: 300,
all the other parameters should be on default settings,
for
Logical channel 3
:
Name
: PID controller,
Mode
: Controller,
Controller num
: 1 PID:"Controller 1",
Set point channel
: Log.ch. 2:"Desired temp",
Feedback channel
: Log.ch. 1:"Temperature",
Precision
: 0,
Graph Lo
: 0,
Graph Hi
: 300,
all the other parameters should be on default settings,
The last thing to do is set of the SSR output.
Enter the
Device configuration
menu, then
Built-in outputs
and select Output:
Out.C2 : OC
. In this output set the parameters as follows:
Mode
: PULSE
Source
: Log.ch. 3:"PID controller",
Level mode
: value,
Lower level
: 0,
Upper level
: 100,
Alarm level
: 0 / heater off if any error occurs/,
Period
: 10sec,
Minimum ON-Time
: 0,
Minimum OFF-Time
: 0,
207