User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
7.8.5.
Logical Channels -
Set point value mode
In the
Set point value
mode the user defines a constant value which can be displayed
on the screen, used for calculations in other channels (e.g. in math functions, controllers etc.)
or as a data source for built-in or external outputs which will control any object.
The parameters of the
Logical channels
in the
Set point value
mode should be:
–
Name
- it gives the name to the logical channel,
–
Mode=Set point value
- in this parameter the user selects a source type of data for
the logical channel,
–
Unit
- this parameter allows the user to define any unit,
–
Set point value
- this parameter is visible only if
Edit button=disabled
, after
pressing the button next to the
Set point value
parameter appears in the window
allowing to enter a value (see
), this value will be a source of data for this
Logical channel.
–
Edit button
- this parameter allows you to activate the button in the panel data
), this parameter has two options:
•
disabled
- the button is disabled on the display, in this case the data source of
the logical channel will be the value set in the
Set point value
parameter,
•
enabled
- this button is active, in this case the data source of the logical channel
will be the value set after pressing the button, but the initial value is the number
written in the
Set point value
parameter, before setting the
Edit button
parameter to
enabled
,
–
Button mode
– the parameter is visible only in case when the
Edit button
parameter is set to
enabled
, and the
Format
parameter in the
Displaying
parameter
block is set to
binary
, it has two options:
•
bistable
– pressing and releasing the button will cause a permanent change of
state,
•
monostable
- pressing and releasing the button will switch from
OFF
state to
ON
state for 0.1 seconds, and after that time it will switch to
OFF
state again,
97
disabled
Hardware input
Hardware output monitor
Modbus
Set point value
Math function
Controller
Profile/timer
Profile/timer (cycle counter)
Data from other channel
Mode
Logical channel
Device configuration
MENU