User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
•
high level
– Profile/timer will be paused when the channel's value in the
Pause
source
parameter is greater than zero ( >0 ) and will be resumed when this
value is lower or equals zero ( ≤0 ). If a Profile/timer is paused and a new trigger
is detected, the Profile/timer will remain in the pause state. Additionally, when in
the
Section list
parameter,
Shape
of
Section num. 1
is set as
const.value
,
then the Profile/timer will set itself on
Final value
of this section, and when in
the
Section list
parameter,
Shape
of
Section num. 1
is set as
slope
, then
the Profile/timer will set itself on its
Idle value
.
•
low level
– Profile/timer will be paused, when the channel's value in the
Pause
source
parameter is lower or equal zero ( ≤0 ) and will be resumed when this
value is greater than zero ( >0 ). If Profile/timer is paused and a new trigger is
detected, the Profile/timer will remain in the pause state. Additionally, when in
the
Section list
parameter,
Shape
of
Section num. 1
is set as
const.value
,
then the Profile/timer will set itself on
Final value
of this section, and when in
the
Section list
parameter,
Shape
of
Section num. 1
is set as
slope
, then
the Profile/timer will set itself on its
Idle value
.
•
rising edge
– Profile/timer will be paused when the device detects the channel's
value change from lower or equal zero ( ≤0 ) to greater than zero ( >0 ) in the
Pause source parameter, and will be resumed when the device detects another
change like that in this channel. If Profile/timer is paused and a new trigger is
detected, the Profile/timer will react to this trigger as if it wan not paused.
•
falling edge
– Profile/timer will be paused when the device detects
the channel's value change from greater than zero ( >0 ) to lower or equal zero (
≤0 ) in the
Pause source
parameter, and will be resumed when the device
detects another change like that in this channel. If Profile/timer is paused and
a new trigger is detected, the Profile/timer will react to this trigger as if it was not
paused.
–
Pause source
– this parameter is not visible when the
Pause mode
parameter is
set as
disabled
. It contains the list of Logical channels, where the selected one will
be a pause source for the Profile/timer,
–
Idle value
– the value before and after generating the defined Profile,
–
Section list
– submenu where the user can define Profile/timer consisting of up to
100 sections. For more details see below in this
Chapter
.
–
Looping
– each Profile has a possibility to repeat its generated signal. This
parameter has the following options:
•
disabled
– the Profile is generated only once,
•
counted
– allows to generate Profile specified number of times defined in
the
Loop count
parameter,
•
from logical channel
– this option allows the user to run a
Profile
a specified
number of times set in the selected logical channel defined by the
Looping source
parameter,
•
infinite
– this option allows the user to repeat the generated
Profile
infinitely,
–
Loop count
– this parameter is visible only when the
Looping
parameter is set on
counted
. It allows the user to enter the number of generated Profile repetitions,
–
Looping source
– this parameter is visible only when the
Looping
parameter is set
on
from logical channe
l. It allows the user to select the logical channel from the list,
whose value will be compared to the number of Profile cycles. If the cycle value is
equal or greater than the value in the logical channel, next repetition of the Profile
will not start,
176