User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
4.2.
ASSEMBLY
- The unit is designed for mounting inside housings (control panel, switchboard)
insuring appropriate protection against surges and interference. Metal
housings must be connected to ground in a way that complies with the
governing regulations.
- Disconnect the power supply prior to starting assembly.
- Check the connections are wired correctly prior to switching the unit on.
- In order to install the unit, a mounting hole must be prepared according to
. The thickness of the material of which the panel is made must not
exceed 5mm. When preparing the mounting hole take the grooves for catches
located on both sides of the housing into consideration (
). Place the
unit in the mounting hole inserting it from the front side of the panel, and then
fix it using the brackets (
). The minimum distances between the centre
points of multiple units - due to the thermal and mechanical conditions of
operation - are shown on
96 x 96 housing:
H, W = 90.5 mm
h = 16 mm
144 x 144 housing:
H, W = 137 mm
h= 38.5 mm
Fig. 4.2. Mounting hole dimensions
12
W
h
8 mm
8 mm
h
1 mm
max. 5 mm
H
1 mm
!
!