User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Most important parameters of UI modules contd.:
UI12
U24
I24
Number of inputs
12xU + 12xI
24xU
24xI
Hardware limitations
voltage inputs
current inputs
0V ÷ 12V
0mA ÷ 24mA
0V ÷ 12V
-
-
0mA ÷ 24mA
Hardware resolution
voltage inputs
current inputs
1mV
1
µ
A
1mV
-
-
1
µ
A
Precision
voltage inputs
current inputs
0,1% @ 25˚C
0,1% @ 25˚C
0,1% @ 25˚C
-
-
0,1% @ 25˚C
Covered
MultiCon CMC-99/141
measurement ranges *
type
max.
type
max.
type
max.
0÷5V
1÷5V
0÷10V
2÷10V
0÷20mA
4÷20mA
0÷6V
0÷6V
0÷12V
0÷12V
0÷22mA
4÷22mA
0÷5V
1÷5V
0÷10V
2÷10V
-
-
0÷6V
0÷6V
0÷12V
0÷12V
-
-
-
-
-
-
0÷20mA
4÷20mA
-
-
-
-
0÷22mA
4÷22mA
Temperature limitations
50 ppm/
˚
C
50 ppm/
˚
C
50 ppm/
˚
C
Internal impedance
voltage inputs
current inputs
50kΩ
type 100Ω
50kΩ
-
-
type 100Ω
Protection
voltage inputs
current inputs
no
50mA auto-reset fuse
no
-
-
50mA auto-reset fuse
Sampling period
10ms
10ms
10ms
Isolation strength
1 min. @ 500V AC
1 min. @ 500V AC
1 min. @ 500V AC
Weight
62 g
68 g
64 g
*
Measurement ranges are limited by software upon hardware inputs ability, check current list of
producer's website
Tab. 8.3 Technical data for the module UI12, U24, I24
238