background image

the heat output see the pressure/heat out-

put  diagrams  for  natural  gas  (methane)

and  butane  or  propane  gas  are  available

(fig. 22 - 22/a).

5.4

CONVERSION 

TO ANOTHER GAS

For the functioning with propane (G31) gas,

a kit with that needed for the conversion is

supplied.

To  convert  from  one  gas  to  another  carry

out the following operations (fig. 23):

– Close the gas cock.

– Undo the burner group

– Replace  the  main  nozzles  (4)  supplied  in

kit,  and  placing  the  copper  washer  (3);  to

carry out this operation use a ø 7 wrench.

– Insert  the  bridge  of  the  “GPL-MET”  con-

nector  of  the  electronic  panel  onto  the

“GPL” position (7 fig. 17).

– For the setting of the values of the maxi-

mum  gas  pressure  and  the  minimum

follow  the  indications  as  specified  in

point 5.2.

Once  the  operating  pressure  changes

have been carried out seal the regula-

tors.

– The  supply  pressure  mus t  never  be

greater than 50 mbar.

– Once  the  operations  have  been  finished

cover,  with  the  label  supplied,  the  gas

pre-setting data on the data tag.

NOTE: After assembly the sealing capaci-

ty of all the gas connections must be test-

ed,  using  special  products,  and  avoiding

the  use  of  naked  flames.  The  conversion

must  be  carried  out  only  by  authorised

personnel.

5.5

DISASSEMBLY 

OF EXPANSION VESSEL

For  disassemble  the  expansion  vessel  pro-

ceed in the following way:

– Make sure that the boiler has been emp-

tied of water

– Unscrew  the  union  that  connects  the

expansion  vessel  and  the  screw  that

release it from its bracket.

Before  beginning  to  fill  the  system,  make

sure  that  the  expansion  vessel  is  pre-filled

to a pressure of 0.8 ÷ 1 bar.

5.6

CLEANING AND MAINTENANCE

Carry  out  the  cleaning  of  the  generator  in

the following way:

– Remove the electricity supply to the boil-

er and close the gas supply cock.

– Dismantle  the  burner  -  gas  manifold

group (fig. 23).

– To  clean  direct  a  stream  of  air  towards

the  inner  part  of  the  burner  to  blow  out

any dust that has accumulated.

– Then clean the heat exchanger removing

dust and combustion deposits.

– In  cleaning  the  heat  exchanger  and  that

of the burner, chemical products or steel

brushes must never be used.

– Make  sure  that  the  top  perforated  part

of the burners is free of encrustations.

– During the assembly and disassembly of

t he  bur ner  it  is  r ecommended  t hat

attention  be  paid  to  the  ignition  and

detection electrodes.

– Reassemble the parts removed from the

boiler,  observing  the  succession  of  the

phases.

– Check the functioning of the main burner.

– After  the  assembly  all  the  gas  connec-

tions must be checked for the seal, using

soapy  water  or  specific  products,  avoid-

ing the use of naked flames.

The programmed maintenance of the gen-

erator is carried out annually.

20

15

10

5

8,1 (7.000) 11,6 (10.000)

17,4 (15.000)

23,2 (20.000)

POTENZA TERMICA kW (kcal/h)

PRESSIONE UGELL

O mbar

25

30

0

29,0 (25.000)

35

A

V

ANT 30/50-30/1

30

18

Pressure/heat output diagram for propane gas (G31)

Fig. 22/a

1

2

3

4

5

6

Fig. 23

KEY
1

Burner manifold        

2

Lock nut 1/2 ” 

3

Washer ø 6,1

4

Nozzle M6

5

Protection            

6

Burners

WARNING: To ensure a
perfect  seal,  always
use the washer (3) sup-
plied  in  the  kit  when
replacing  nozzles,  even
in  burner  units  for
which  it  is  not  speci-
fied.

N

OZZLE

PRESSURE

(mbar)

HEAT OUTPUT kW (Btu/h)

8,1 (27.600)

11,6 (39.600)

17,4 (59.350)

23,2 (79.150)

29,0 (98.950)

Содержание Planet Super 4 F.S.

Страница 1: ...Planet Super 4 F S Installation Servicing Instructions GB...

Страница 2: ...itted and adjusted Has the system and boiler been flushed Is the system and boiler full of water and the correct pressure showing on the pressure gauge Are the Auto Air Vent open Has the pump been rot...

Страница 3: ...tiometer of 60 C for a maximum period of 10 minutes The gas flow refers to the inferior calorific value in standard conditions of 15 C 1013 mbar 4 F S Heat output Nominal kW 29 0 Btu h 98 950 Minimum...

Страница 4: ...Magnesium anode 19 D H W safety valve 21 D H W expansion vessel 22 D H W tank drain cock 23 Water pressure transducer 24 C H safety valve 25 D H W cock 26 C H return cock 27 C H flow cock 28 Gas cock...

Страница 5: ...designed and con structed specifically for this purpose An existing cupboard or compartment may be used provided it is modified accordingly Where installation will be in an unusual location special p...

Страница 6: ...e case of bathroom installations for domestic boilers where the point of connection to the mains MUST be outside of the bathroom 2 7 WATER SYSTEMS GENERAL This appliance is designed for connection to...

Страница 7: ...t access to the outside wall 3 2 1 Flue air duct lengths Determine whether an extension duct is required with reference to the flue lengths information given in Table 3 If no extension ducts are requi...

Страница 8: ...l kit is used A wall liner 127 mm 5 in internal diam eter 500 mm 19 in long is available as an optional extra for use when fitting the flue air duct from inside the build ing or where it is required t...

Страница 9: ...building or in cold indoor environments insulation is necessary to prevent burner ignition failure In such cases provide for con densate drainage If a segment of the flue passes through a flammable w...

Страница 10: ...ing from the failure to pro vide for proper earthing of the appliance 3 7 1 Room stat connection To gain access to the TA CR SE SB J2 electronic board connector remove the control panel cover and conn...

Страница 11: ...coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode TS 100 C safety stat PF Smoke pressure switch V Fan TPA Water pressure transducer PI C H pump PB D H W pump SE External sensor TA Ro...

Страница 12: ...fety Functions Delivery temperature control guided by the atmospheric conditions taking into account the dynamics of the building Delivery temperature control guided by atmospheric conditions with inf...

Страница 13: ...e influence must be increased If the ambient temperature is around the pre set value control oscillation the influence must be reduced Note If the ambient temperature influence constant is set at 0 th...

Страница 14: ...y programmable input terminals 3 and 4 of the socket allows three different functions to be activated The parameter has the following significance 1 If an external sensor is connected the display will...

Страница 15: ...ical pause by the burner of around 90 seconds both at the beginning when the plant is cold and in the subsequent startings This is so to avoid ignitions and switching off with very short intervals tha...

Страница 16: ...nition a continuous jump spark from the electrode is noted despite the burner being lit After 10 sec onds the sparking stops the burner goes off and the block signal lights up The cable of the detecto...

Страница 17: ...WITH ZONE VALVES CIRCUIT WITH ZONE PUMPS Pump cable J2 connector NOTE Relays are used only if the zone valves have no microswitches NOTE Replace the C H pump with the optional connecting pipe code 80...

Страница 18: ...to the values indicated in Table 6 The setting of the gas pressure at minimum and maximum values is carried out by SIME variations are dis couraged Only in the passing from one type of gas supply meth...

Страница 19: ...e turn the nut clockwise Turn off and turn on the boiler a few times whilst keeping the hot water cock constantly open to verify that the pres sure corresponds to the values given in Table 6 After hav...

Страница 20: ...he expansion vessel is pre filled to a pressure of 0 8 1 bar 5 6 CLEANING AND MAINTENANCE Carry out the cleaning of the generator in the following way Remove the electricity supply to the boil er and...

Страница 21: ...at the radiator valves or eventual zone valves are open The test may be carried out also during hot water functioning To do so it is enough after having activated the chimney sweep function to take so...

Страница 22: ...40 5 828 50 4 161 60 3 021 70 2 229 80 1 669 6 9 Printed Circuit Board Re hang control panel as described in 5 6 1 Remove control panel cover Pull of the potentiometer knobs Remove all connections to...

Страница 23: ...ot tap to clear the air from DHW pipe work Check for water soundness 7 2 Commissioning Turn the rotary switch to the summer posi tion Check gas pressures as described in 5 2 Allow cylinder to achieve...

Страница 24: ...et 17x24x2 58 6120511 Nipple 3 4 x3 4 OT 59 6216008 D H W storage tank outlet pipe 60 6017210 Manual air vent 1 4 61 6227614 Pipe connecting D H W expans vessel 62 6124808 Circulating pump Grundfos UP...

Страница 25: ...Fan 37 6229220 Fan mounting plate Position Code Description 38 6235800 Venturi pressure nipple 39 6235804 Pressure test nipple M6 40 6229101 Smoke pressure switch bracket 41 6225710 Air pressure switc...

Страница 26: ...l supporting bracket 94 6281600 Control panel 95 6273200 Guidelight 12 ways out 96 6273201 Guidelight 6 ways out 97 6230682 Main PCB with ignition 98 6201501 Trimmer spindle 5 Position Code Descriptio...

Страница 27: ......

Страница 28: ...Cod 6258912 Documentation Dpt Sime Ltd Unit D2 Enterprise Way Bradford Road Bradford West Yorkshire BD10 8EW Tel 0870 9911114 Fax 0870 9911115 www sime ltd uk e mail enquiries sime ltd uk...

Страница 29: ...Planet Super 4 F S User Instructions GB...

Страница 30: ......

Страница 31: ...e is displayed on the scale of the red leds from 40 80 C Regulation of the C H temperature is carried out by acting on the heating knob The set temperature is shown on the scale of the red leds from 4...

Страница 32: ...system until the green led 1 bar lights up If all the leds are off call the authorised technical staff Safety stat interception fig 5 If the safety stat intercedes the red led 35 C intermittently ligh...

Страница 33: ...ss h to change the hour on the display or m to change the minutes To set the day press the 1 7 button until the arrow is pointing to the correct day 1 Monday 7 Sunday Setting the program The time cloc...

Страница 34: ...e load hot water Fig 11 Fig 9 Deleting one or more programs fig 8 The on and off time must be deleted for each program to be deleted Set selector 2 to position P Select the desired program with button...

Страница 35: ...the fol lowing list of items one after the other are displayed The thermosensor continues to function independently of the display Day hour room temperature External temperature D H W temperature Thi...

Страница 36: ...water at reduced level To have access to the reduced D H W temperature parameter press the and keys at the same time for at least 5 seconds and then go along the entered lines with the key until para...

Страница 37: ...perature of the D H W tank is regulated to the value set with user parameter n 3 In the reduced areas of heating the temperature of the D H W tank is regulated to the value set with parameter n 61 of...

Страница 38: ...Vacation period 1 10 18 Vacation function To enter the number of days of absence In the display the vacation symbol will be shown on the left the day of activa tion 1 Monday 7 Sunday and on the right...

Страница 39: ...water pressure Restore functioning by filling the boiler System overpressure Call the authorised technical staff for assistance Safety stat interception Call the authorised technical staff for assist...

Страница 40: ...Cod 6258913 Documentation Dpt Sime Ltd Unit D2 Enterprise Way Bradford Road Bradford West Yorkshire BD10 8EW Tel 0870 9911114 Fax 0870 9911115 www sime ltd uk e mail enquiries sime ltd uk...

Страница 41: ...Planet Super 4 W M...

Страница 42: ...as a correct by pass been fitted and adjusted Has the system and boiler been flushed Is the system and boiler full of water and the correct pressure showing on the pressure gauge Are the Auto Air Vent...

Страница 43: ...ditions of 15 C 1013 mbar Differential measure between the pressure upstream of the gas valve and the depression in sealed chamber 30 60 BF Heat output Nominal kW 11 6 29 5 Btu h 39 600 100 650 Minimu...

Страница 44: ...cock optional 19 C H return cock optional 20 C H flow cock optional 21 D H W cock optional 22 D H W tank drain cock 23 D H W sensor SB 24 85 C limit stat 25 Magnesium anode 26 Filling cock 27 Non retu...

Страница 45: ...designed and con structed specifically for this purpose An existing cupboard or compartment may be used provided it is modified accordingly Where installation will be in an unusual location special p...

Страница 46: ...installations for domestic boilers where the point of connection to the mains MUST be outside of the bathroom 2 7 WATER SYSTEMS GENERAL This appliance is designed for connection to sealed central heat...

Страница 47: ...meter with a 1 mm wall thickness 3 3 1 Flue air duct lengths Determine whether an extension duct is required with reference to the Z dimen sion shown in fig 8 Alternatively max flue lengths informa ti...

Страница 48: ...EM IS TO BE TREATED IN THE FOLLOWING CASES Very extensive system with high con tents of feedwater Frequent addition of makeup water into the system Should it be necessary to empty the sys tem either p...

Страница 49: ...an horizontal outlet 3 7 3 Roof outlet coaxial duct The roof outlet terminal L 1280 cannot be shortened and the positioning of the tile dis tances must be no less than 600 mm from the discharge termin...

Страница 50: ...mm fig 16 The accessories necessary for this type of discharge and some of the other type of systems that it is possible to use are shown in fig 16 By utilising the doubler fitting 7 fig 17 it is pos...

Страница 51: ...s flow splitting unit with take off points code 8093000 2a 90 elbow MF code 8077404 2b Isolated 90 elbow MF code 8077408 3a Extension L 1000 code 8077303 3b Isolated extension L 1000 code8077306 4 Int...

Страница 52: ...with sections of 0 25 square mm and for lengths greater than 50 m use cables with sections of 0 5 square mm First of all assemble and cable the socket 2 and then insert the apparatus that will start...

Страница 53: ...heric conditions taking into account the dynamics of the building Delivery temperature control guided by atmospheric conditions with influence of ambient temperature Ambient temperature control only A...

Страница 54: ...ature from the pre set value remains high during the entire day the influence must be increased If the ambient temperature is around the pre set value control oscillation the influence must be reduced...

Страница 55: ...y programmable input terminals 3 and 4 of the socket allows three different functions to be activated The parameter has the following significance 1 If an external sensor is connected the display will...

Страница 56: ...d the boiler is ready to function with METHANE with the connector connected with LPG Connector ANN RIT 5 fig 22 The electronic panel is programmed in heating phase with a technical pause by the burner...

Страница 57: ...circuit Red led flashing in case of C H safety valve interception Red led flashing lack of communication with the Logica Remote Control Red led on ignition failure Turn the selector CR OFF EST INV UN...

Страница 58: ...ll in electricity the burner is immediately arrested once the electricity is restored the boiler will automatically restart 4 4 SMOKE PRESSURE SWITCH The switch with a fixed setting 3 5 4 5 mm H2O is...

Страница 59: ...ations are dis couraged Only in the passing from one type of gas supply methane to another butane or propane is a change in the working pressure allowed It is essential that this operation is car ried...

Страница 60: ...he nut clockwise Turn off and turn on the boiler a few times whilst keeping the hot water cock constantly open to verify that the pres sure corresponds to the values given in Table 6 Reconnect the ele...

Страница 61: ...mp tied of water Unscrew the union that connects the expansion vessel and the screw that release it from its bracket Before beginning to fill the system make sure that the expansion vessel is pre fill...

Страница 62: ...intenance of the gen erator is carried out annually 4 7 1 Chimney sweep function To carry out the verification of combustion in the boiler turn the selector and stop on the position until the yellow l...

Страница 63: ...64 65 66 Value 5 6 C 15 16 C 0 14 15 70 80 C 7 5 C min 0 0 0 0 immaterial 0 0 1 0 0 0 immaterial WITH EXTERNAL TEMPERAT SENSOR WITHOUT EXTERNAL TEMPERAT SENSOR Function 15 51 52 53 54 55 56 57 58 59 6...

Страница 64: ...ng pump UPS 15 50 D H W 6124808 7 Circulating pump UPS 15 60 C H 6124806 8 Air pressure switch 6225710 9 Sensing electrode 6235916 10 Ignition electrode 6235915 KEY DESCRIPTION MAKER S PT NO 11 D H W...

Страница 65: ...carried out by acting on the heating knob The set temperature is shown on the scale of the red leds from 40 80 C To guarantee an always optimal output from the generator it is advised not to go below...

Страница 66: ...g act on the filling cock until the green led 1 bar lights up Once filled close the filling tap If all the leds are off call the authorised technical staff Safety stat interception fig 5 If the safety...

Страница 67: ...acing the selector on the or posi tion obviously without consequent con trol of the room temperature The functioning instructions are inside the lid fig 8 Every setting or modifica tion is displayed a...

Страница 68: ...the fol lowing list of items one after the other are displayed The thermosensor continues to function independently of the display Day hour room temperature External temperature D H W temperature Thi...

Страница 69: ...water at reduced level To have access to the reduced D H W temperature parameter press the and keys at the same time for at least 5 seconds and then go along the entered lines with the key until para...

Страница 70: ...mperature of the D H W tank is regulated to the value set with user parameter n 3 In the reduced areas of heating the temperature of the D H W tank is regulated to the value set with parameter n 61 of...

Страница 71: ...riod 1 10 18 Vacation function To enter the number of days of absence In the display the vacation symbol will be shown on the left the day of activa tion 1 Monday 7 Sunday and on the right the number...

Страница 72: ...re Restore functioning by acting on the filling cock of the boiler fig 4 System overpressure Call the authorised technical staff for assistance Safety stat interception Call the authorised technical s...

Страница 73: ...d in depth technical training courses FREE LUNCH Certificate on completion of the course Please fill in the form below for more details Combination Boilers Name Address Postcode Tel No Company Please...

Страница 74: ......

Страница 75: ......

Страница 76: ...nderie Sime S p A via Garbo 27 37045 Legnago Vr Tel 0442 631111 Fax Serv Commerciale Italia 0442 631291 Fax Serv Tecnico 0442 631292 Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime S...

Отзывы: