ANOMALIES AND SOLUTIONS
When. there. is. a. functioning. anomaly,. the.
display.shows.an.alarm.and.the.blue.lumi-
nous.bar.becomes.red.
Descriptions.of.the.anomalies.with.the.rela-
tive.alarms.and.solutions.are.given.below:
–. ALARM 02 (fig. 27/a)
.
If. the. water. pressure. detected. is. lower.
than.0.5.bar,.the.boiler.will.stop.and.the.
display.will.show.“ALL.02”.
. Bring. the. pressure. back. to. normal. by.
means.of.the.load.faucet.until.the.pres-
sure. indicated. by. the. transducer. is.
between.1.and.1.5.bars.
. ON. COMPLETION. OF. THE. OPERATION,.
MAKE.SURE.THE.LOAD.FAUCET.IS.CLO-
SED.
. If it is necessary to repeat the system
loading procedure, it is advisable to
contact qualified technical personnel to
check the seal of the heating system (to
check whether there are any leaks).
–. ALL 03
. Request assistance from qualified tech-
nical personnel.
–. ALL 05
. Request assistance from qualified tech-
nical personnel.
–. ALL 06 (fig. 27/c)
.
Press.the.key
.
5
3
1
2
4
.
f.the.controls.(2).to.
re-start.the.boiler.
If the anomaly persists, request assi-
stance from qualified technical person-
nel.
–. ALL 07 (fig. 27/d)
.
Press.the.key
.
5
3
1
2
4
.
of.the.controls.(2).to.
re-start.the.boiler.
. If the anomaly persists, request assi-
stance from qualified technical person-
nel.
–. ALL 08
.
Request assistance from qualified tech-
nical personnel.
–. ALL 09
. Request assistance from qualified tech-
nical personnel.
–. ALL 10
.
Request assistance from qualified tech-
nical personnel.
–. ALL 13 (fig. 27/e)
. Press.the.key.
5
3
1
2
4
.
of.the.controls.(2).to.
re-start.the.boiler.
.
If the anomaly persists, request assi-
stance from qualified technical person-
nel.
–. ALL 14
.
Request assistance from qualified tech-
nical personnel.
–. ALL 15
.
Request assistance from qualified tech-
nical personnel.
–. From “ALL 20” to “ALL 29”
.
Request assistance from qualified tech-
nical personnel.
GREEN LED PUMP
HIGH EFFICIENCY (fig. 28)
If.the.LED.(1).signal.is.missing.or.the.colour.
changes. (blinking. red/green. or. blinking.
red),.contact.an.authorised.technician.
If,.on.the.other.hand,.the.LED.(1).is.steady.
red,.restart.manually.by.pressing.the.but-
ton.(4).for.5.seconds,.then.release.it..
If. the. pump. does. not. restart,. request. the.
intervention.of.authorised.technical.staff.
GAS CONVERSION
If. it. is. necessary. to. change. to. a. different.
type. of. gas,. request. assistance. only. from.
authorised.technical.personnel.
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..27/d
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..27/a
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..27/e
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Apre
2
2
2
Circuito
riscaldamento 2
Circuito
riscaldamento 3
(impianto tre
zone)
Fig..27/c
1
2
3
4
Fig..28
Содержание MURELLE HE 25-30 ErP
Страница 2: ......
Страница 109: ...109 ES PT ENG NOTES...
Страница 110: ...110 NOTES...
Страница 111: ......