Technical Documentation
51
users manual inverter SE3.3Ni - SE3.8Ni - SE4.6Ni
5.2 Technical Specifications:
CE Marking.
Electrical Safety Directive EN 50178.
Electromagnetic Compatibility Directive.
EN 61000-6-4: EN 55011
EN 61000-6-2: EN 61000-4-2
EN 61000-4-4
Complies with RD 661/2007, RD 1663/2000, DK 5940 and VDE 0126-1-1.
Standards
Due to our continuous improvement policy, these specifications are subject to change without prior notice.
Anti-island protection.
Protection against leakage currents.
Protection against reverse polarity.
Protection against short circuits.
Protections
100-450 V
DC
500 V
DC
Maximum DC power
MPP Voltage range
Maximum voltage range
Maximum current
Number of MPPTs
Maximum number of Strings
DC Input
4,5 kWp
5 kWp
20 A (2x10A)
SE3.3Ni
SE3.8Ni
SE4.6Ni
6 kWp
20 A (2x10A)
30 A (3x10A)
1-2
1-2
1-3
2
2
3
AC Output
Nominal power
Maximum power
Maximum effective current
Nominal voltage
Nominal frequency
Harmonic distortion (THD)
Power factor
Galvanic insulation
Number of phases
3,3 kW
3,8 kW
16,52 A
3,8 kW
4,4 kW
19,13 A
230 VAC
50 Hz
<3%
>0,99
Assured by RCMU*
Single phase
4,6 kW
5,1 kW
22 A
SE3.3Ni
SE3.8Ni
SE4.6Ni
* RCMU: Residual Current Monitoring Unit.
General characteristics
IP 65
<1 W
Forced ventilation
LED / LCD
RS232C / RS485
580 x 422 x 182 mm.
-20ºC to +55ºC (without derating)
Maximum 95%
MC4
RST25i3
22,5 Kg.
23 Kg.
Yield maximum
Yield UE
Level of protection
Own consumption (stand by)
Cooling system
Display
Comunications
Dimensions
Weight
Operating temperature
Ambient humidity
Type of DC connection
Type of AC connection
SE3.3Ni
SE3.8Ni
SE4.6Ni
22,5 Kg.
96,3%
95,1%
95,1%
95,4%
96,3%
96,2%
Содержание SE3.3Ni
Страница 1: ...nverters...
Страница 8: ...ror Messages n ations on 44 44 47 50 50 51 52 53...
Страница 25: ...Installation user s manual inverter SE3 3Ni SE3 8Ni SE4 6Ni 6 Pin Number of the Waterproof RJ 45 plug...
Страница 26: ...25 3 7 Assembly of the Waterproof RJ 45 plug...
Страница 28: ...27 2 4 2 Parallel configuration of inverter incorrect 7...
Страница 56: ...55...
Страница 57: ...Notes user s manual inverter SE3 3Ni SE3 8Ni SE4 6Ni...
Страница 58: ......