![Silicon Graphics Prism Скачать руководство пользователя страница 223](http://html.mh-extra.com/html/silicon-graphics/prism/prism_user-manual_1271592223.webp)
Pre-Installation Activities
007-4701-003
201
7.
Measure between the ground socket and an appropriate earth-ground location and ensure that
resistance is less than 1 ohm.
8.
Repeat steps 1 through 7 for any additional single-phase power receptacles.
Caution: If a voltage reading is incorrect, or if the resistance measured in step 7 is more than 1
ohm, contact a site-approved electrician. Do not proceed with the installation.
Figure C-2
32-amp Single-phase Power Plug for International Sites
!
Power cord
connector
Socket 1
(line)
Ground socket
Socket 2
(neutral)
Receptacle
Pin 2 (neutral)
Ground pin
Pin 1 (line)