H49.0.02.6C-02
Operating Manual MH 3750
Page 7
7/11
Supported interface functions:
Code
Name/Function
Code
Name/Function
0
read nominal value
200
read min. display range
3
read system status
201
read max. display range
6
read min. value
202
read unit of display
7
read max. value
204
read decimal point of display
12
read ID-no.
208
read channel count
22
read min. alarm rail (AL. - AL.Lo)
214
read scale correction
23
read max. alarm rail (AL. - AL.Hi)
215
set scale correction
216
read zero displacement
217
set zero displacement
32
read configuration flag
alarm function: 1; Alarm horn:3;
BitLoggerOn:50; BitCyclicLogger:51;
224
Logger: read data cyclic logger
102
set min. alarm rail (AL. - AL.Lo)
225
Logger: read cycle time (LoGG - CYCL)
103
set max. alarm rail (AL. - AL.Hi)
226
Logger: set cycle time (LoGG - CYCL)
160
set configuration flag (see 32)
227
Logger: start recording
174
delete min. value
228
Logger: read #of data
175
delete max. value
229
Logger: read status
176
read min measuring range
231
Logger: read stop time
177
read max measuring range
233
read Real time clock (CLOC)
178
read measuring range unit
234
set Real time clock (CLOC)
179
read measuring range decimal point
236
Read logger memory size
180
read measuring type
240
Reset
194
set display unit
254
read program identification
199
read meas. type in display
260
Logger: read data manual logger
4.5.2 Analogue Output – Scaling with DAC.0 and DAC.1
With the DAC.0 and DAC.1 values the output can be rapidly scaled to Your efforts.
Keep in mind not to connect low-resistive loads to the output, otherwise the output value will be wrong and battery life is
decreased. Loads above ca 10kOhm are uncritical.
If the display exceeds the value set by DAC.1, then the device will apply 1V to the output
If the display falls below the value set by DAC.0, then the device will apply 0V to the output
In case of an error (Err.1, Err.2, no sensor, etc.) the device will apply slightly above 1V to the output.
GND
plug wiring::
+Uout
Attention!
The 3
rd
contact has to be left floating!
Only stereo plugs are allowed!
4.6 Alarm
There are three possible settings: Alarm off (AL. oFF), on with horn sound (AL. on), on without horn sound (AL. no.So).
Following conditions will display an alarm, when the function is activated (on or no.So):
-
Value is below lower (AL. Lo) or above upper alarm rail (AL.Hi).
-
Sensor error
-
Low battery (bAt)
-
Err.7: System error (always with sound)
In case of an alarm and when polling the interface the prio-flag is set in the returned interface message.
4.7 Real Time Clock
The real time clock is used for the logger function: Recorded values are also containing the point of time, when they
were measured. Please check the settings when necessary.
If the battery was replaced the referring menu ‚CLOC‘ will automatically be started.
SIKA, Dr. Siebert & Kühn GmbH & Co. KG, Struthweg 7-9, 34260 Kaufungen, Germany
Tel: +49-5605-803-0, Fax: +49-5605-803-54, email: [email protected], web: www.SIKA.net