1
Installation and Setting Instructions
Electronic Programmable and Non-Programmable Fan Coil Thermostats
6000 series with independent fan common
Specifi cation
Power supply:
24 volt powered models
- 20-30 Vac, 50/60Hz
230 volt powered models
- 210-250 Vac, 50/60Hz
Temperature range:
Heating stage - Off -5-30°C
Cooling stage - 16-37°C-Off
Temperature accuracy:
± 0.5°C
Deadzone adjustment:
1, 2, 3 or 4°C
Voltage rating of contacts:
20-250 Vac, 50/60Hz
Current rating of contacts:
10mA - 3A resistive, 1A inductive
Switching action:
Voltage free SPDT contacts, Type 1B
Time accuracy:
± 1 minute
Memory retention:
24V & 230V models: 15 days
Battery model: 1 minute for battery change
IP rating:
IP30
Dimensions (mm):
130 x 100 x 38 (W x H x D)
Control pollution situation:
Degree 2
Rated impulse voltage:
2.5 KV
Ball pressure test:
75°C
Applications
HC & HCT Models
Features
24 volt
230 volt
Type Code Type Code
Heat or cool operation, selectable at time of installation
3-speed fan output
HCS6101-3
087N722500
Heat & cool systems (with auto changeover), for use in 4-pipe systems
3-speed fan output
HCT6113-3
087N759326
HC & HCT Models with 3 speed fan
(4 pipe auto change-over)
HCS & HCST Models with 3 speed fan
(Heat or Cool)
HCS & HCST Models
Wiring
Ordering Details