53
Siemens Building Technologies
Fire Safety & Security Products
10.2008
NOTE
If no route failures are detected, the self-test log shows the total routes tested. If failures are detected,
only the failures are shown.
Self-test results
A full list of all the possible self-test results is shown in Tab. 41. The actual test
records provided depend on the tests that you ran after you selected the
Test
Type
and the
Test Level
during the VisiPC Self-test Request.
All test record listings include a Results Summary, as the last record.
Test Description
Result Type
Result Data
Address Decoder Test Results
PLD firmware version
Firmware versions
Latest version supported,
actual version read
PLD register integrity
Register values
Value written and value read
FLASH Test Results
FLASH boot loader FLASH CRC
None
None
Controller FLASH CRC
None
None
FPGA/Font FLASH CRC/Checksum
Firmware area
Font area
Not Tested; or
Checksum Passed; or
CRC Passed; or
Test Failed
User configuration CRC/checksum
Fixed area
Variable area
Factory defaults
Not Tested; or
Checksum Passed; or
CRC Passed; or
Test Failed
Power Supply Test Results
+12 V supply
Voltage read
Voltage
-5 V supply
Voltage read
Voltage
VBATT supply
Voltage read
Voltage
SRAM Test Results
Static RAM size
Memory size
detected
Size in kilobytes
Battery-Backed SRAM Test Results
Command status data validation
None
None
RTC Test Results
Timer interrupt period
Period measured
Period in ms
RTC Register integrity
Bad registers
Register count and first bad value
SCB Subsystem Test Results
SCB Register integrity
Location of first bad
register
Register offset from start of SCB
Master/slave connection
None
None
CPU Temperature Test Results
CPU temperature
Temperature read
Degrees C
Serial Ports Test Results (up to 21 sets of internal loopback results, one per communication channel)
Serial channel (n) sent (byte count), received
(byte count) bytes (internal loopback)
[
Data transmission and reception
]
Total bytes received
Channel number (n),
Byte count sent,
Bytes received.
Serial channel (n) data integrity: (byte count)
bytes not matched (internal loopback)
[
Data integrity]
Total bytes not
matching
Channel
number
(n),
Byte count.
Serial Ports Test Results (up to 21 sets of external loopback results, one per communication channel
Data transmission and reception
Total bytes received
Channel number,
Byte count sent,
Bytes received.
Data integrity
Total bytes not
matching
Channel
number,
Byte count.