41 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Parameters
23.09.2010
4.8
Multistate Output Mapping (Static)
MO(X)_STATIC_(X)CHA_(X)
(SIMATIC Manager hardware catalog)
Parameter for mapping the multistate process value to a specific number of output
channels.
We distinguish between three different [MO(n)_Static] function types. The following
table shows the channels in regard to function and representation in the SIMATIC
Manager hardware catalog:
Channels
Relevant submodules,
representation in the Simatic Manager hardware catalog
2-channel MO2_Static_2Cha_St1
MO2_Static_2Cha_St2
3-channel MO3_Static_3Cha_St1
MO3_Static_3Cha_St2
MO3_Static_3Cha_St3
4-channel MO4_Static_4Cha_St1
MO4_Static_4Cha_St2
MO4_Static_4Cha_St3
MO4_Static_4Cha_St4
Important
These function groups must be inserted in the subslots
without any changes to the order
and
in direct succession to each other.
4.8.1
Mapping Function 1:n
Parameter for mapping the multistate process
value to a single active output channel in
accordance with the parameter [MappingTable].
Only a single output can ever be active.
In the case of an invalid [MOValue] (i.e., no
corresponding value was found in
[MappingTable],
a quality error message (Reliability) is
generated [Quality = MULTISTATE_FAULT]
a backup value becomes valid according to the
value in [BackupMode].
Duplicate assignments in the [MappingTable]
are not detected by the I/O function. Only the
value that is found first determines the output
channel.
Representation
Definition,
addition
Function and
representation of the
channels
Definition,
addition