Technical
Data
Spurious emission
(residential and industrial areas)
:
Comments
Standard
Limit values
Burst pulses on data and
signal lines:
IEC 61000-4-4
1 kV
(RS232 interface)
2 kV (remaining data and
signal lines)
Electrostatic discharge (ESD)
IEC 61000-4-2
6 kV
Electrostatic air discharge
(ESD)
IEC 61000-4-2
8 kV
Surge voltage / Surge on
power supply lines
3
IEC 61000-4-5
+ 2 kV asymmetrical
+ 1 kV symmetrical
Surge on data and signal
lines:
IEC 61000-4-5
+ 1 kV asym.
(to cable shielding)
HF irradiation
(electromagnetic fields)
IEC 61000-4-3
26 MHz to 1000 MHz and 1.4 to
2.0 GHz 10 V/m (80% AM with
1 kHz)
900 MHz and 1.89 GHz
Up to 10 V/m (50% PM)
Cable fed interferences
Data, signal and power supply
lines
IEC 61000-4-6
0.15 kHz – 80 MHz
10 Veff (80% AM 1 kHz)
Damped vibration
on power supply line
EN 61000-4-12
1 MHz
1.0 kV symmetrical
1.0 kV asymmetric
Refresh rate: 1 sec.
Duration 10 min.
Voltage interruptions
the power supply
EN 61000-4-29
Interruption time:
0...20 ms
Refresh rate:
1 s
(Load cell impedance
≥
85 Ohm)
Table 11-11
Data: Electromagnetic Compatibility
1
The module must be mounted on a grounded metal frame. The S7-200 must be grounded directly over
the metal frame. With the exception of the 24 V power supply line, shielded cable must be used for all
lines. The cable shielding must be grounded on both ends at low resistance.
2
The S7-200 must be installed in a closed metal housing. For all cables, shielded cable must be used. The
cable shielding must be grounded on both ends at low resistance.
3
To meet requirements, an external protection element should be used (e.g.: Blitzductor VT
AD24V, by Dehn&Söhne)