Alarm, error and system messages
9.2 Messages
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
187
9.2
Messages
Icon
Error message
Cause/ measures
Pressure simulation
Measured values do not correspond to the actual measured values of the
application. To resume measurement, deactivate simulation mode.
"2.3.2 Pres. Simulation" (Page 102).
Current simulation
Measured values do not correspond to the actual measured values of the
application. To resume measurement, deactivate simulation mode.
"2.3.1 Output Current" (Page 102).
Device operating system fault
There is a fault in the operating system. The application electronics must be
replaced. Please contact Siemens Support.
EEPROM device fault
There is a fault in the electronics. The application electronics must be re-
placed. Please contact Siemens Support.
Firmware device fault
There is a fault in the application electronics. Please contact Siemens Sup-
port.
Hardware device fault
There is a mechanical defect in the pressure transmitter. The application
electronics must be replaced. Check your application.
RAM device fault
There is a fault in the electronics. The application electronics must be re-
placed. Please contact Siemens Support.
ROM device fault
There is a fault in the electronics. The application electronics must be re-
placed. Please contact Siemens Support.
Watchdog device fault
The watchdog function of the pressure transmitter has failed. The applica-
tion electronics must be replaced. Please contact Siemens Support.
Technical support (Page 227)
EEPROM sensor fault
There is a fault in the measuring cell electronics. The measuring cell must
be replaced. Please contact Siemens Support.
Hardware sensor fault
There is an electrical defect in the measuring cell. The measuring cell must
be replaced. Please contact Siemens Support.
RAM sensor fault
There is a fault in the measuring cell electronics. The measuring cell must
be replaced. Please contact Siemens Support.
ROM sensor fault
There is a fault in the measuring cell electronics. The measuring cell must
be replaced. Please contact Siemens Support.
Firmware sensor fault
There is a fault in the measuring cell electronics. The measuring cell must
be replaced. Please contact Siemens Support. .
Technical support (Page 227)
Analog signal unreliable
Shows the status of the analog signal. Check the connection, supply lead
and power supply of the pressure transmitter.
Measurement unreliable
Shows the status of the measured values. Check the further messages.
Sensor break
Measuring cell may be damaged beyond repair. Check your application and
replace the measuring cell, if necessary.
Device maintenance alarm
Service the device immediately or reset the service timer.
Sensor maintenance alarm
Service the sensor immediately or reset the service timer.
Device service request
Service the device without delay or reset the service timer.
Содержание SITRANS P500
Страница 1: ......
Страница 2: ......
Страница 10: ...Table of contents SITRANS P500 with HART 10 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 14: ...Introduction 1 6 Notes on warranty SITRANS P500 with HART 14 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 214: ...Technical data 11 9 HART communication SITRANS P500 with HART 214 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 218: ...Dimension drawings 12 2 Level SITRANS P500 with HART 218 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 221: ...Appendix A 3 Overview SITRANS P500 with HART Operating Instructions 12 2014 A5E02344528 09 221 Continued on next page ...
Страница 222: ...Appendix A 3 Overview SITRANS P500 with HART 222 Operating Instructions 12 2014 A5E02344528 09 Continued on next page ...
Страница 223: ...Appendix A 3 Overview SITRANS P500 with HART Operating Instructions 12 2014 A5E02344528 09 223 Continued on next page ...
Страница 224: ...Appendix A 3 Overview SITRANS P500 with HART 224 Operating Instructions 12 2014 A5E02344528 09 Continued on next page ...
Страница 225: ...Appendix A 3 Overview SITRANS P500 with HART Operating Instructions 12 2014 A5E02344528 09 225 Continued on next page ...
Страница 226: ...Appendix A 3 Overview SITRANS P500 with HART 226 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 228: ...Appendix A 4 Technical support SITRANS P500 with HART 228 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 230: ...List of abbreviations SITRANS P500 with HART 230 Operating Instructions 12 2014 A5E02344528 09 ...
Страница 234: ...Glossary SITRANS P500 with HART 234 Operating Instructions 12 2014 A5E02344528 09 TP Total Performance ...
Страница 238: ......