Page 84
SITRANS LR 300– INSTRUCTION MANUAL
7ML19985CL02
mmm
mm
Communicat
ions
Point Data (R41,010 – R41,031)
Measurement point data contain the current instrument readings. These are the values
shown for the reading measurement, (level, distance, or volume, according to the setting
for P001); and for the volume measurement, (volume). Please see page 56 for more
details on P001.
The available registers are:
The reading is expressed as a percentage of full scale, multiplied by 100:
Input/Output
The SITRANS LR 300 has one mA output.
mA Output (R41,110)
The mA output is scaled from 400 to 2,000 (4 to 20 mA multiplied by 100). Displayed in
P911.
Parameter Access (R43,997 – R46,999)
Parameter values are given as integers in the range of registers from R44,000 to R44,999.
The last three numbers of the register correspond to the parameter number.
Data
Registers
Parameter
Reading
41,010 P920
Volume
41,020
P924
Reading
Value
0
0.00%
5000
50.00%
7564
75.64%
20,000
200.00%
Parameter Register #
Parameter #
44,000
P000
44,001
P001
44,002
P002
…
…
44,999
P999
SITRANS LR 300.book Page 84 Monday, June 10, 2002 7:18 PM
Содержание SITRANS LR 300
Страница 1: ...SITRANS LR 300 Instruction Manual ITRANS LR 30 July 2002 ...
Страница 14: ...Page 12 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Specifications ...
Страница 46: ...Page 44 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Start Up ...
Страница 96: ...Page 94 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Troubleshooting ...
Страница 136: ...Page 134 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Appendix VIII ...
Страница 139: ......
Страница 140: ... 7ml19985cl02 Siemens Milltronics Process Instruments Inc 2002 Subject to change without prior notice Rev 2 4 ...