Page 68
SITRANS LR 300 – INSTRUCTION MANUAL
7ML19985CL02
mmm
mm
Pa
ra
m
et
er
s
Range Calibration Parameter (P655)
P655 Propagation Factor (F = 1)
Compensates for the change in the microwave velocity as compared with propagation in
free space, when propagation is within a stillpipe (metal).
Consult Technical Assistance at the factory for other sizes and propagation factor
numbers.
Values
Range:
0.0000 to 1.0000
Pre-set: 1
Pipe Size (I.D.) Propagation Factor
50 mm (2”)
0.827
80 mm (3”)
0.915
100 mm (4”)
0.955
150 mm (6”)
0.980
200 mm (8”)
0.990
Note:
For waveguide antennas used as stillpipes, the propagation factor value is
shown on the process device tag.
10.42 m
The propagation factor is constant for a given pipe
diameter,
or can be determined by comparing the
radar distance reading to the actual process
material distance (measured from the face of the
SITRANS LR 300 flange).
Example:
actual distance =
p.f.
(propagation
SITRANS LR 300 distance
factor)
Using the readings shown:
10.42m = 0.827
12.6m
Enter the propagation factor : 0.827
SITRANS LR 300 distance
SITRANS LR 300.book Page 68 Monday, June 10, 2002 7:18 PM
Содержание SITRANS LR 300
Страница 1: ...SITRANS LR 300 Instruction Manual ITRANS LR 30 July 2002 ...
Страница 14: ...Page 12 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Specifications ...
Страница 46: ...Page 44 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Start Up ...
Страница 96: ...Page 94 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Troubleshooting ...
Страница 136: ...Page 134 SITRANS LR 300 INSTRUCTION MANUAL 7ML19985CL02 mmmmm Appendix VIII ...
Страница 139: ......
Страница 140: ... 7ml19985cl02 Siemens Milltronics Process Instruments Inc 2002 Subject to change without prior notice Rev 2 4 ...