76
PBD-51041388
SITRANS LG250 - Operating Instructions
46201-EN-150424
Starting current
≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA
Load
see load diagram under Power supply
Damping (63 % of the input variable),
adjustable
0 … 999 s
HART output values according to HART 7 (default setting)
1)
Ʋ
First HART value (PV)
Linearised percentage value, level
Ʋ
Second HART value (SV)
Distance to the level
Ʋ
Third HART value (TV)
Measurement certainty, level
Ʋ
Fourth HART value (QV)
Electronics temperature
Indication value - DIsplay and adjustment module
2)
Ʋ
Displayed value 1
Filling height Level
Ʋ
Displayed value 2
Electronics temperature
Resolution, digital
< 1 mm (0.039 in)
Output variable - Additional current output
For details on the operating voltage see chapter "Voltage supply"
Output signal
4 … 20 mA (passive)
Range of the output signal
3.8 … 20.5 mA (default setting)
Signal resolution
0.3 µA
Failure signal current output (adjustable)
Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
Max. output current
21.5 mA
Starting current
≤ 10 mA for 20 ms after switching on, ≤ 3.6 mA
Load
Load resistor, see chapter "Voltage supply"
Damping (63 % of the input variable),
adjustable
0 … 999 s
Indication value - DIsplay and adjustment module
3)
Ʋ
Displayed value 1
Filling height Level
Ʋ
Displayed value 2
Electronics temperature
Resolution, digital
< 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ
Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ
Relative humidity
45 … 75 %
Ʋ
Air pressure
+860 … +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)
Installation reference conditions
Ʋ Min. distance to internal installations
> 500 mm (19.69 in)
1)
The output values can be assigned individually
2)
The indication values can be assigned individually
3)
The indication values can be assigned individually