SITRANS LG250 - Operating Instructions
46201-EN-150424
In the menu item "
Current output mode
" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
In the menu item "
Current output Min./Max.
", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
If a supplementary electronics with an additional current output is
implemented in the instrument, you can adjust the additional current
output separately.
In menu item"
Current output 2
" you specify which measured value
the additional current output refers to.
The additional current output cannot be used as an output in the
sense of a safety-instrumented application (SIL).
The procedure corresponds to the previous settings of the standard
current output. See "
Setup - Current output
".
Since the HART variables are very extensive, the indication was
divided into two menu items.
Setup - Current output
mode
Setup - Current output
Min./Max.
Setup - Current output 2
Setup - HART variables