SITRANS LG250 - Operating Instructions
46201-EN-150424
This menu item is only available if you have selected interface meas-
urement under the menu item "
Application
". In this menu item you can
choose the type of medium of the upper medium.
You can enter the dielectric constant of the upper medium directly or
have the value determined by the instrument. To do this you have to
enter the measured or known distance to the interface.
In this menu item you can enter the max. adjustment for the level. With
interface measurement this is the maximum total level.
Adjust the requested percentage value with
[+]
and store with
[OK]
.
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
reference plane (seal surface of the process fitting). Keep in mind that
the max. level must lie below the dead band.
In this menu item you can enter the min. adjustment for the level. With
interface measurement this is the minimum total level.
Adjust the requested percentage value with
[+]
and store with
[OK]
.
Setup - Application - Di-
electric constant
Setup - Max. adjustment
Level
Setup - Min. adjustment
Level