Page 74
SITRANS LC500 – OPERATING INSTRUCTIONS
7ML19985GE04
Appendix A
Range Inversion
Displays whether the device is operating with a normal or inverted range setting.
A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the
LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV
(Menu 0F): the LCD displays inv.
1. Set the rotary switch to 9.
2. Press both buttons simultaneously for more than one second to toggle between
the two modes, effectively switching the values for LRV and URV.
Keylock Level
Controls the access protection level for the device. The factory setting is a local
protection level of 0, which places no restriction on modifying settings locally.
•
Protection level 1 disables the ability to set a value by pressing two buttons
simultaneously.
•
Protection level 2 disables the ability to change a value by stepping it up or down.
•
Protection level 3 completely disables all changing of values.
1. Set the rotary switch to F.
2. Press the RED (+) or BLUE (–) button to change the setting.
Menu
Item
Rotary
Switch
Position
Left Arrow
Description
Mode
Values
19
9
On
Range Inversion
normal
*
Display shows nor
inverted
Display shows inv
Note:
HART settings override local settings:
•
If the HART setting is 0, there are no restrictions, and you cannot change the
protection to a higher level locally.
•
If the HART setting is 3, no changes can be made, and this protection level cannot
be changed locally.
Menu
Item
Rotary
Switch
Position
Left
Arrow
Protection
Display
Level
Description
local
settings
HART
settings
1F
F
On
0
*
No restrictions
PL 0
No restrictions
PH 0
1
Disables 2-button
adjustments
PL 1
PH 1
2
Disables 1-button
adjustments
PL 2
PH 2
3
Disables all
changes
PL 3
PH 3