Page 60
SITRANS LC500 – OPERATING INSTRUCTIONS
7ML19985GE04
Appendix A
Upper Range Value
Upper Range Value (URV) is the setting for 100% of the operating range, in most cases a
full vessel/tank. The transmitter variable on which this menu selection operates is chosen
in Menu 01. For TV0, the URV is in most cases Factory Set to the probe capacitance in
water.
The increment/decrement step size is subject to the setting from Menu 09.
1. Set the rotary switch to F.
2. Press and hold both buttons simultaneously to take the current PV reading as
the new setting.
or: Press the RED (+) or BLUE(–) button to step this value up or down.
or: Press and hold a button for a prolonged time to start a repeat function.
When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value
is rejected, and the previous value remains unchanged.
Transmitter Variable Values: menu level 0
Dynamic Value, Primary Variable (PV): menu 00 and menu 10
The value for the Primary Variable is displayed as either units or percent of range,
selected in menu 01. When 2-state mode is selected in menu 07 the LCD display indicates
the probe status:
•
blinking for an uncovered probe
•
steady for a covered probe
If the internal diagnostics detect a fault or failure, the display alternates between the PV
value and the fault/failure message ‘Flt’. If the product level goes outside the limit settings,
then the display alternates between the PV value and ‘ooL’. Alternatively, if the simulation
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode Description
Values
0F
01, 09, 0B, 0C
F
Off
Analog
Upper Range Value
Range: 3300 to
0
Factory setting
Probe capaci-
tance in water
Display percent
Display shows
- - - -
Note:
Menus 00 and 10 are the only locations where you can change from level 1 to
level 0, or vice versa.