FFT to determine the flow rate. The Reflexor mode will operate with many of the same sensors
that are used with transit-time flow measurement along with those which are specifically
designed for Doppler flow measurement. Use of any other sensor than shown in these
instructions may result in failure to measure or give an incorrect flow rate indication.
Typical Installation
The typical steps to complete the Reflexor installation procedure are as follows:
1. Collect the site data (pipe and liquid data, part numbers, etc.).
2. Choose a mounting location for the flow sensors.
3. Prepare the pipe for sensor’s mounting.
4. Access the Installation Menu and create a site.
5. Enter the pipe parameters.
6. Mount flow sensors on pipe and connect to flowmeter.
7. Invoke the sensor installation procedure.
8. Optimize installation through use of the Spectra Display and diagnostic data.
Almost all menu cells will contain default parameters and will not require any additional action.
To obtain operation you will only need to access the menu cells for required parameters, such
as pipe data. Obtaining accurate flow rate data will take less than five minutes.
Application conditions may require you to mount the sensors using the adjacent mounting
method as described and shown in this section.
Selecting a Sensor Set
Maximum sensitivity will be obtained with use of the 191N1S sensor set.
Alternative sensors recommended for use by Reflexor include:
● 1011 Universal size C1, C2 and C3
● 1011 HP-T1 size B1H and A3H
● 1011 HP-T2 size B1H and A3H
● 1011 HP-T3 size B1H and A3H
● 991 Universal size 2 and 3A High and Very High Temperature versions
● 990 (991 Sensor)
The sensor models are also available for submersible and extended temperature applications.
Functions
7.11 Reflexor
FUP1010 IP67 Portable Flowmeter
Operating Instructions, 02/2010, A5E02951522A Revision 01
97
Содержание SITRANS FUP1010
Страница 2: ......
Страница 66: ......
Страница 136: ......
Страница 138: ......
Страница 150: ......
Страница 153: ...1010WP 7 21614 C ...
Страница 154: ...1010WP 7 21614 C ...
Страница 155: ...1010WDP 7 21614 C ...
Страница 156: ...1010WDP 7 21614 C ...
Страница 157: ...1010WP 8 21614 C ...
Страница 158: ...1010WDP 8 21614 C ...
Страница 159: ......
Страница 161: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Страница 162: ...1011PPS 8 TRANSDUCER PART NUMBER L H W NET WT PAIR X Z 21614 C SIZES A B C D SIZE E ...
Страница 163: ...21614 C ...
Страница 164: ......
Страница 165: ......
Страница 166: ......
Страница 167: ......
Страница 168: ...21614 C ...
Страница 169: ...21614 C ...
Страница 170: ...21614 C ...
Страница 171: ...21614 C ...
Страница 172: ...21614 C ...
Страница 173: ...21614 C ...
Страница 174: ...21614 C ...
Страница 175: ...1015BC 1W 8 21614 C ...
Страница 176: ......
Страница 177: ...21614 C ...
Страница 178: ...21614 C ...
Страница 179: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Страница 180: ...REFLECT MODE DIRECT MODE 21614 C ...
Страница 181: ...21614 C ...
Страница 182: ...1015BC 1 8 21614 C ...
Страница 183: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Страница 184: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Страница 185: ......
Страница 186: ......
Страница 187: ......
Страница 188: ......
Страница 190: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Страница 191: ......
Страница 192: ......
Страница 193: ...L TEMPERATURE BELOW 225 F ONLY SUITABLE FOR AMBIENT TEMPERATURE GLAND SUPPLIED WITH CABLE IS 21614 C PART No L ...
Страница 194: ......
Страница 204: ......
Страница 206: ......
Страница 207: ......