1. FAULT – When selected the system will declare the Reflexor channel to be in Fault and
the flowmeter will indicate "F" on the display screen. Note that when a new Reflexor channel
is created the [Fault] option is the default mode. Also note that the sum (or difference)
channel will also be declared to be in Fault.
2. ZERO – When selected the Reflexor channel will be declared to be at Zero Flow instead
of in Fault and the flowmeter will indicate 0.00 on the display screen.
7.5
Setting Relays
Relay Functions
Use the [Relay Setup] menu to assign a function to channel relays. The flowmeter supports
two types of relay outputs, Alarm Relay and Pulse Relay. Alarm Relay outputs operate in "fail-
safe" mode. The relay(s) are energized under normal conditions - an alarm condition causes
the relay(s) to de-energize until the alarm clears. The Pulse Relay output supports Totalizer
and batch relay functions, with an output pulse width of approximately 200 ms; maximum
activation rate is 2.5 pulses per sec. If Totalizer pulses exceed this rate, excess pulses are
stored in an overflow register. This allows the relay to "catch up" when flow decreases enough.
Note
Using the <F1> key (Totalizer clear command) also clears all channel Totalizers plus the
overflow register described in the last paragraph.
Relay 1 and 2 Function Assignments
The flowmeter, depending upon the model, provides at least two alarm relays. Please refer to
the Appendix (Page 137) for wiring details. Relays respond to any of the alarm conditions or
data functions included on the Relay Option List.
Table 7-4
Relay Option List
Not Used
Not Active
Power Off
Power Off alarm occurs when power fails.
High Temp
High temperature value relay trip-point.
Low Temp
Low temperature value relay trip-point.
High Flow
System flow rate exceeds high flow set point.
Low Flow
System flow rate falls below low flow set point.
Flow Alarm
System flow rate exceeds or falls below flow set points.
Fault Alarm
System loses receive signal (all paths in fault).
Soft Fault
Fault condition - memory mode active.
Spacing
System sensor spacing needs adjusting.
Empty
Empty pipe alarm.
Aeration
Aeration percentage exceeds alarm set point.
Reverse Flow
Flow is in negative direction.
Functions
7.5 Setting Relays
FUP1010 IP67 Portable Flowmeter
84
Operating Instructions, 02/2010, A5E02951522A Revision 01
Содержание SITRANS FUP1010
Страница 2: ......
Страница 66: ......
Страница 136: ......
Страница 138: ......
Страница 150: ......
Страница 153: ...1010WP 7 21614 C ...
Страница 154: ...1010WP 7 21614 C ...
Страница 155: ...1010WDP 7 21614 C ...
Страница 156: ...1010WDP 7 21614 C ...
Страница 157: ...1010WP 8 21614 C ...
Страница 158: ...1010WDP 8 21614 C ...
Страница 159: ......
Страница 161: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Страница 162: ...1011PPS 8 TRANSDUCER PART NUMBER L H W NET WT PAIR X Z 21614 C SIZES A B C D SIZE E ...
Страница 163: ...21614 C ...
Страница 164: ......
Страница 165: ......
Страница 166: ......
Страница 167: ......
Страница 168: ...21614 C ...
Страница 169: ...21614 C ...
Страница 170: ...21614 C ...
Страница 171: ...21614 C ...
Страница 172: ...21614 C ...
Страница 173: ...21614 C ...
Страница 174: ...21614 C ...
Страница 175: ...1015BC 1W 8 21614 C ...
Страница 176: ......
Страница 177: ...21614 C ...
Страница 178: ...21614 C ...
Страница 179: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Страница 180: ...REFLECT MODE DIRECT MODE 21614 C ...
Страница 181: ...21614 C ...
Страница 182: ...1015BC 1 8 21614 C ...
Страница 183: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Страница 184: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Страница 185: ......
Страница 186: ......
Страница 187: ......
Страница 188: ......
Страница 190: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Страница 191: ......
Страница 192: ......
Страница 193: ...L TEMPERATURE BELOW 225 F ONLY SUITABLE FOR AMBIENT TEMPERATURE GLAND SUPPLIED WITH CABLE IS 21614 C PART No L ...
Страница 194: ......
Страница 204: ......
Страница 206: ......
Страница 207: ......