FEC920: USER GUIDE
Page 64
September 18
6.2.2 Archiving
This area of configuration is used to set up the parameters for use during unattended archiving. Some of the
fields appear only if other fields are set to a particular value. For example, the CSV fields appear only if ‘File
Format’ is set to ‘CSV’ or to ‘Both’.
The archived data is not removed from the flash memory of the instrument. When the flash memory is full, new
data causes the oldest file(s) to be discarded.
Figure 60 Unattended Archive configuration (typical settings)
Media Size
Appears only for File Format = ‘Binary (UHH)’. A read only value showing the capacity of
the memory stick inserted in the USB port at the rear of the unit. Shows zero if no memory
stick is present.
Media Free
Appears only for File Format = ‘Binary (UHH)’. A read only value showing the space
remaining in the memory stick inserted in the USB port at the rear of the unit. Shows zero
if no memory stick is present.
Media Duration
Appears only for File Format = ‘Binary (UHH)’. A read only value showing the time it will
take to fill the Memory stick if the instrument configuration remains unchanged.
Note:
For remote archiving, the host computer must be set up to respond to ‘pings’. This is because
the
FEC920
pings the host whilst establishing connection, and if it does not receive a
response, the archive attempt fails.
1907.46
MB
1902.90
MB
763.77
Days
Automatic
FTP server
Binary (UHH)
Overwrite
Media Size
Media Free
Media Duration
Rate
Destination
File Format
On Media Full
Network.Archiving
/archive
123.123.123.123
history
******
234.234.234.234
anonymous
****
No
None
Remote Path
Primary Server
Primary User
Primary Password
Sec. Server
Sec. User
Sec. Password
Trigger
Period
CSV Date Format
CSV Tab Del
On Media Full
Remote Path
Primary Server
Primary User
Primary Password
Sec. Server
Sec. User
Sec. Password
Trigger
Period
Text
No
Overwrite
/archive
123.123.123.123
history
******
234.234.234.234
anonymous
****
No
None
Monthly
USB
Both
Yes
No
No
Yes
Rate
Destination
File Format
CSV Values
CSV Messages
CSV Headers
CSV Headings
Network.Archiving
Remote with Binary file format
Local with CSV files included
A5E45696052A Rev-AA
Содержание SITRANS FEC920
Страница 1: ...Flow Energy Calculator FEC920 User Guide A5E45696052A Rev AA September 2018 ...
Страница 247: ......