Parameter path
Description
Type
Hex
Dec
Resolution
FEC920: USER GUIDE
Page 148
September 18
ModbusMaster.10.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c90
31888
2dp
ModbusMaster.10.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bf1
31729
Not applicable
ModbusMaster.10.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7b9e
31646
0dp
ModbusMaster.10.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7da4
32164
Not applicable
ModbusMaster.10.Data.Number
Used for multiple instance parameters
uint8
7d1c
32028
Not applicable
ModbusMaster.10.Data.ParameterList
Parameter list for a specific slave device
uint8
7cfe
31998
Not applicable
ModbusMaster.10.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c2d
31789
Not applicable
ModbusMaster.10.Data.PV
Process value received from slave device
float32
7b44
31556
2dp
ModbusMaster.10.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d3a
32058
Not applicable
ModbusMaster.10.Data.Send
1 = send the write value to the slave
bool
7cc2
31938
Not applicable
ModbusMaster.10.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7e04
32260
Not applicable
ModbusMaster.10.Data.SlaveDevice
Slave device to communicate with.
uint8
7b1d
31517
Not applicable
ModbusMaster.10.Data.Status
Transaction status (as for Modbus Master.1
uint8
7ce0
31968
Not applicable
ModbusMaster.10.Data.Value
The value to be written to the slave device
float32
7c54
31828
2dp
ModbusMaster.11.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dc5
32197
Not applicable
ModbusMaster.11.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d59
32089
Not applicable
ModbusMaster.11.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7de5
32229
Not applicable
ModbusMaster.11.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c10
31760
Not applicable
ModbusMaster.11.Data.Descriptor
Description for this data item
string_t
6759
26457
Not applicable
ModbusMaster.11.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e25
32293
Not applicable
ModbusMaster.11.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c92
31890
2dp
ModbusMaster.11.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bf2
31730
Not applicable
ModbusMaster.11.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7bc0
31680
0dp
ModbusMaster.11.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7da5
32165
Not applicable
ModbusMaster.11.Data.Number
Used for multiple instance parameters
uint8
7d1d
32029
Not applicable
ModbusMaster.11.Data.ParameterList
Parameter list for a specific slave device
uint8
7cff
31999
Not applicable
ModbusMaster.11.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c2e
31790
Not applicable
ModbusMaster.11.Data.PV
Process value received from slave device
float32
7b46
31558
2dp
ModbusMaster.11.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d3b
32059
Not applicable
ModbusMaster.11.Data.Send
1 = send the write value to the slave
bool
7cc3
31939
Not applicable
ModbusMaster.11.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7e05
32261
Not applicable
ModbusMaster.11.Data.SlaveDevice
Slave device to communicate with.
uint8
7b1e
31518
Not applicable
ModbusMaster.11.Data.Status
Transaction status (as for Modbus Master.1
uint8
7ce1
31969
Not applicable
ModbusMaster.11.Data.Value
The value to be written to the slave device
float32
7c56
31830
2dp
ModbusMaster.12.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dc6
32198
Not applicable
ModbusMaster.12.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d5a
32090
Not applicable
ModbusMaster.12.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7de6
32230
Not applicable
ModbusMaster.12.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c11
31761
Not applicable
ModbusMaster.12.Data.Descriptor
Description for this data item
string_t
676e
26478
Not applicable
ModbusMaster.12.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e26
32294
Not applicable
ModbusMaster.12.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c94
31892
2dp
ModbusMaster.12.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bf3
31731
Not applicable
ModbusMaster.12.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7bc2
31682
0dp
ModbusMaster.12.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7da6
32166
Not applicable
ModbusMaster.12.Data.Number
Used for multiple instance parameters
uint8
7d1e
32030
Not applicable
ModbusMaster.12.Data.ParameterList
Parameter list for a specific slave device
uint8
7d00
32000
Not applicable
ModbusMaster.12.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c2f
31791
Not applicable
ModbusMaster.12.Data.PV
Process value received from slave device
float32
7b48
31560
2dp
ModbusMaster.12.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d3c
32060
Not applicable
ModbusMaster.12.Data.Send
1 = send the write value to the slave
bool
7cc4
31940
Not applicable
ModbusMaster.12.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7e06
32262
Not applicable
ModbusMaster.12.Data.SlaveDevice
Slave device to communicate with.
uint8
7b1f
31519
Not applicable
ModbusMaster.12.Data.Status
Transaction status (as for Modbus Master.1
uint8
7ce2
31970
Not applicable
ModbusMaster.12.Data.Value
The value to be written to the slave device
float32
7c58
31832
2dp
ModbusMaster.13.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dc7
32199
Not applicable
ModbusMaster.13.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d5b
32091
Not applicable
ModbusMaster.13.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7de7
32231
Not applicable
ModbusMaster.13.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c12
31762
Not applicable
ModbusMaster.13.Data.Descriptor
Description for this data item
string_t
6783
26499
Not applicable
ModbusMaster.13.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e27
32295
Not applicable
ModbusMaster.13.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c96
31894
2dp
ModbusMaster.13.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bf4
31732
Not applicable
ModbusMaster.13.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7bc4
31684
0dp
ModbusMaster.13.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7da7
32167
Not applicable
ModbusMaster.13.Data.Number
Used for multiple instance parameters
uint8
7d1f
32031
Not applicable
ModbusMaster.13.Data.ParameterList
Parameter list for a specific slave device
uint8
7d01
32001
Not applicable
ModbusMaster.13.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c30
31792
Not applicable
ModbusMaster.13.Data.PV
Process value received from slave device
float32
7b4a
31562
2dp
ModbusMaster.13.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d3d
32061
Not applicable
ModbusMaster.13.Data.Send
1 = send the write value to the slave
bool
7cc5
31941
Not applicable
ModbusMaster.13.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7e07
32263
Not applicable
ModbusMaster.13.Data.SlaveDevice
Slave device to communicate with.
uint8
7b20
31520
Not applicable
ModbusMaster.13.Data.Status
Transaction status (as for Modbus Master.1
uint8
7ce3
31971
Not applicable
ModbusMaster.13.Data.Value
The value to be written to the slave device
float32
7c5a
31834
2dp
ModbusMaster.14.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dc8
32200
Not applicable
ModbusMaster.14.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d5c
32092
Not applicable
ModbusMaster.14.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7de8
32232
Not applicable
A5E45696052A Rev-AA