Parameter path
Description
Type
Hex
Dec
Resolution
FEC920: USER GUIDE
Page 146
September 18
ModbusMaster.2.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c25
31781
Not applicable
ModbusMaster.2.Data.PV
Process value received from slave device
float32
7b34
31540
2dp
ModbusMaster.2.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d32
32050
Not applicable
ModbusMaster.2.Data.Send
1 = send the write value to the slave
bool
7cba
31930
Not applicable
ModbusMaster.2.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7dfc
32252
Not applicable
ModbusMaster.2.Data.SlaveDevice
Slave device to communicate with.
uint8
7b15
31509
Not applicable
ModbusMaster.2.Data.Status
Transaction status (as for Modbus Master.1)
uint8
7cd8
31960
Not applicable
ModbusMaster.2.Data.Value
The value to be written to the slave device
float32
7c44
31812
2dp
ModbusMaster.3.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dbd
32189
Not applicable
ModbusMaster.3.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d51
32081
Not applicable
ModbusMaster.3.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7ddd
32221
Not applicable
ModbusMaster.3.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c08
31752
Not applicable
ModbusMaster.3.Data.Descriptor
Description for this data item
string_t
66b1
26289
Not applicable
ModbusMaster.3.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e1d
32285
Not applicable
ModbusMaster.3.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c82
31874
2dp
ModbusMaster.3.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bea
31722
Not applicable
ModbusMaster.3.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7b90
31632
0dp
ModbusMaster.3.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7d9d
32157
Not applicable
ModbusMaster.3.Data.Number
Used for multiple instance parameters
uint8
7d15
32021
Not applicable
ModbusMaster.3.Data.ParameterList
Parameter list for a specific slave device
uint8
7cf7
31991
Not applicable
ModbusMaster.3.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c26
31782
Not applicable
ModbusMaster.3.Data.PV
Process value received from slave device
float32
7b36
31542
2dp
ModbusMaster.3.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d33
32051
Not applicable
ModbusMaster.3.Data.Send
1 = send the write value to the slave
bool
7cbb
31931
Not applicable
ModbusMaster.3.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7dfd
32253
Not applicable
ModbusMaster.3.Data.SlaveDevice
Slave device to communicate with.
uint8
7b16
31510
Not applicable
ModbusMaster.3.Data.Status
Transaction status (as for Modbus Master.1
uint8
7cd9
31961
Not applicable
ModbusMaster.3.Data.Value
The value to be written to the slave device
float32
7c46
31814
2dp
ModbusMaster.4.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dbe
32190
Not applicable
ModbusMaster.4.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d52
32082
Not applicable
ModbusMaster.4.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7dde
32222
Not applicable
ModbusMaster.4.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c09
31753
Not applicable
ModbusMaster.4.Data.Descriptor
Description for this data item
string_t
66c6
26310
Not applicable
ModbusMaster.4.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e1e
32286
Not applicable
ModbusMaster.4.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c84
31876
2dp
ModbusMaster.4.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7beb
31723
Not applicable
ModbusMaster.4.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7b92
31634
0dp
ModbusMaster.4.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7d9e
32158
Not applicable
ModbusMaster.4.Data.Number
Used for multiple instance parameters
uint8
7d16
32022
Not applicable
ModbusMaster.4.Data.ParameterList
Parameter list for a specific slave device
uint8
7cf8
31992
Not applicable
ModbusMaster.4.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c27
31783
Not applicable
ModbusMaster.4.Data.PV
Process value received from slave device
float32
7b38
31544
2dp
ModbusMaster.4.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d34
32052
Not applicable
ModbusMaster.4.Data.Send
1 = send the write value to the slave
bool
7cbc
31932
Not applicable
ModbusMaster.4.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7dfe
32254
Not applicable
ModbusMaster.4.Data.SlaveDevice
Slave device to communicate with.
uint8
7b17
31511
Not applicable
ModbusMaster.4.Data.Status
Transaction status (as for Modbus Master.1
uint8
7cda
31962
Not applicable
ModbusMaster.4.Data.Value
The value to be written to the slave device
float32
7c48
31816
2dp
ModbusMaster.5.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dbf
32191
Not applicable
ModbusMaster.5.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d53
32083
Not applicable
ModbusMaster.5.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7ddf
32223
Not applicable
ModbusMaster.5.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c0a
31754
Not applicable
ModbusMaster.5.Data.Descriptor
Description for this data item
string_t
66db
26331
Not applicable
ModbusMaster.5.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e1f
32287
Not applicable
ModbusMaster.5.Data.FallBackValue
Fall back value to be written into the slave device
float32
7c86
31878
2dp
ModbusMaster.5.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bec
31724
Not applicable
ModbusMaster.5.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7b94
31636
0dp
ModbusMaster.5.Data.Mode
Auto Manual mode selection (0 = Auto; 1 = Manual)
uint8
7d9f
32159
Not applicable
ModbusMaster.5.Data.Number
Used for multiple instance parameters
uint8
7d17
32023
Not applicable
ModbusMaster.5.Data.ParameterList
Parameter list for a specific slave device
uint8
7cf9
31993
Not applicable
ModbusMaster.5.Data.Priority
Read/Write frequency (as for Modbus Master.1)
uint8
7c28
31784
Not applicable
ModbusMaster.5.Data.PV
Process value received from slave device
float32
7b3a
31546
2dp
ModbusMaster.5.Data.Scaling
Scaling in decimal places for non floating point data types
uint8
7d35
32053
Not applicable
ModbusMaster.5.Data.Send
1 = send the write value to the slave
bool
7cbd
31933
Not applicable
ModbusMaster.5.Data.Set
Sets a digital value (1 = on; 0 = off)
bool
7dff
32255
Not applicable
ModbusMaster.5.Data.SlaveDevice
Slave device to communicate with.
uint8
7b18
31512
Not applicable
ModbusMaster.5.Data.Status
Transaction status (as for Modbus Master.1
uint8
7cdb
31963
Not applicable
ModbusMaster.5.Data.Value
The value to be written to the slave device
float32
7c4a
31818
2dp
ModbusMaster.6.Data.AlarmStatus
Alarm status (as for Modbus Master.1)
uint8
7dc0
32192
Not applicable
ModbusMaster.6.Data.BitPosition
Bit position of the bit of interest in a 16 bit data type
uint8
7d54
32084
Not applicable
ModbusMaster.6.Data.ChanAlarmStatus
Channel alarm status (as for Modbus Master.1)
uint8
7de0
32224
Not applicable
ModbusMaster.6.Data.DataType
Type of data being read/written (as for Modbus Master.1)
uint8
7c0b
31755
Not applicable
ModbusMaster.6.Data.Descriptor
Description for this data item
string_t
66f0
26352
Not applicable
ModbusMaster.6.Data.Digital
Digital status (0 = Off, 1 = On)
bool
7e20
32288
Not applicable
ModbusMaster.6.Data.FallBackValue
Fall back value to be written to the slave device
float32
7c88
31880
2dp
ModbusMaster.6.Data.FunctionCode
The Modbus function code (as for Modbus Master.1)
uint8
7bed
31725
Not applicable
ModbusMaster.6.Data.ModbusAddress
Modbus register address of the data to be read/written
float32
7b96
31638
0dp
A5E45696052A Rev-AA
Содержание SITRANS FEC920
Страница 1: ...Flow Energy Calculator FEC920 User Guide A5E45696052A Rev AA September 2018 ...