6. Connect wires to terminals using wiring tool, wall mount transmitter.
PROFIBUS DP/PA
④
In + (B)
⑤
In - (A)
⑥
Out + (B)
⑦
Out - (A)
7. Tighten cable gland.
5.2.2.6
Connecting channels 2 to 4
Channel 2 is for output only and channels 3 to 4 can be connected as either inputs/outputs or
relays, see Input/output configuration (Page 81)
Connect wires
1. Remove cap and ferrule from cable gland and slide onto cable.
Wall mount enclosure: Remove blind plug and fit cable gland.
2. Push cable through open gland and cable path.
3. Restore ferrule and tighten cap to lightly hold cable in place.
4. Fold signal cable screen back over outer sheath and ground beneath cable clamp.
In case of shielded cables, use metal cable glands for proper connection.
5. Connect wires to terminals using screwdriver.
6. Tighten cable gland.
The numbers in the graphics below refer to table Figure 5-3 Termination/configuration
Connecting
5.2 Connecting FC430
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
79
Содержание SITRANS FC430
Страница 40: ...Description 3 5 Theory of operation FC430 From firmware 4 0 40 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 94: ...Connecting 5 4 Device nameplates FC430 From firmware 4 0 94 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 150: ...Operating FC430 7 2 HMI FC430 From firmware 4 0 150 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 182: ...Functions 8 16 Maintenance FC430 From firmware 4 0 182 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 262: ...Dimensions and weight 12 5 Mounting bracket FC430 From firmware 4 0 262 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 534: ...Index FC430 From firmware 4 0 534 Operating Instructions 06 2017 A5E39789392 AA ...