4.2.2
Sensor installation
4.2.2.1
Determining a location
CAUTION
Electromagnetic fields
Do not install the flowmeter in the vicinity of strong electromagnetic fields, for example near
motors, variable frequency drives, transformers etc.
Upstream / downstream
● No pipe run requirements, that is straight inlet/outlet sections are not necessary.
● Avoid long drop lines downstream from the sensor to prevent process media separation
causing air / vapor bubbles in the tube (min. back pressure: 0.2 Bar).
● Avoid installing the flowmeter immediately upstream of a free discharge in a drop line.
Installing/mounting
4.2 Installation instructions
FC430 (From firmware 4.0)
54
Operating Instructions, 06/2017, A5E39789392-AA