![Siemens SITRANS FC430 Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/siemens/sitrans-fc430/sitrans-fc430_operating-instructions-manual_374486076.webp)
6. Connect wires to terminals, wall mount transmitter.
)
)
Active current output
Passive current output
5
Ca+
6
Cp-
4
C
5
C
7. Tighten cable gland.
Note
For Ex versions active or passive current output is preselected at ordering and cannot be
changed.
Non-Ex versions can be connected as either active or passive.
Note
Load
Signal output: < 500 Ω at 14 to 24 VDC (active), 14 to 30 VDC (passive)
Relay output: 30 VAC/VDC, 100 mA
Passive signal input: 15 to 30 VDC, 2 to 15 mA
Table 5-1
HW polling address
Load [Ω] Voltage (active
Ex) [V]
Voltage (active non
Ex) [V]
24 V DC Voltage supply (passive) [V] Ex and
Non Ex
Measurered
100
3
3
17.7
200
5.9
5.9
19.6
500
11.4
14.9
21.0
1000
14.8
19.2
21.6
2000
17.4
20.1
21.9
5000
19.4
20.4
22.2
10000
20.3
21
22.3
20000
20
20.4
22.4
50000
20.4
20.6
22.5
100000 20.6
20.7
22.6
Connecting
5.2 Connecting FC430
FC430 (From firmware 4.0)
76
Operating Instructions, 06/2017, A5E39789392-AA
Содержание SITRANS FC430
Страница 40: ...Description 3 5 Theory of operation FC430 From firmware 4 0 40 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 94: ...Connecting 5 4 Device nameplates FC430 From firmware 4 0 94 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 150: ...Operating FC430 7 2 HMI FC430 From firmware 4 0 150 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 182: ...Functions 8 16 Maintenance FC430 From firmware 4 0 182 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 262: ...Dimensions and weight 12 5 Mounting bracket FC430 From firmware 4 0 262 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 534: ...Index FC430 From firmware 4 0 534 Operating Instructions 06 2017 A5E39789392 AA ...