![Siemens SITRANS FC430 Скачать руководство пользователя страница 525](http://html.mh-extra.com/html/siemens/sitrans-fc430/sitrans-fc430_operating-instructions-manual_374486525.webp)
HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
4.3.5
Parity and framing
Select parity and stop bit config‐
uration.
Even parity, 1
stopbit
● Even parity, 1
stopbit
● Odd parity, 1
stopbit
● No parity, 2
stopbits
User
4.3.6
Floating point byte order Select byte transmission se‐
quence
3-2-1-0
● 1-0-3-2
● 0-1-2-3
● 2-3-0-1
● 3-2-1-0
User
4.3.7
Integer byte order
Select byte transmission se‐
quence
MSB – LSB (big
endian)
● MSB – LSB
(big endian)
● LSB – MSB
(little endian)
4.3.8
Register mapping
4.3.8.1
Enable mapping
Mark up to 20 register mappings.
4.3.8.2
Source register 1
Requested register communica‐
ted via Modbus.
65535
0 to 65535
User
4.3.8.3
Target register 1
Register of an existing product
parameter which the Modbus re‐
quest is redirected to.
65535
0 to 65535
User
4.3.8.4
Source register 2
Requested register communica‐
ted via Modbus.
65535
0 to 65535
User
4.3.8.5
Target register 2
Register of an existing product
parameter which the Modbus re‐
quest is redirected to.
65535
0 to 65535
User
4.3.8.6
Source register 3
Requested register communica‐
ted via Modbus.
65535
0 to 65535
User
4.3.8.7
Target register 3
Register of an existing product
parameter which the Modbus re‐
quest is redirected to.
65535
0 to 65535
User
4.3.8.8
Source register 4
Requested register communica‐
ted via Modbus.
65535
0 to 65535
User
4.3.8.9
Target register 4
Register of an existing product
parameter which the Modbus re‐
quest is redirected to.
65535
0 to 65535
User
4.3.8.10
Source register 5
Requested register communica‐
ted via Modbus.
65535
0 to 65535
User
4.3.8.11
Target register 5
Register of an existing product
parameter which the Modbus re‐
quest is redirected to.
65535
0 to 65535
User
4.3.8.12
Source register 6
Requested register communica‐
ted via Modbus.
65535
0 to 65535
User
4.3.8.13
Target register 6
Register of an existing product
parameter which the Modbus re‐
quest is redirected to.
65535
0 to 65535
User
Default settings
E.12 Communication
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
525
Содержание SITRANS FC430
Страница 40: ...Description 3 5 Theory of operation FC430 From firmware 4 0 40 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 94: ...Connecting 5 4 Device nameplates FC430 From firmware 4 0 94 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 150: ...Operating FC430 7 2 HMI FC430 From firmware 4 0 150 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 182: ...Functions 8 16 Maintenance FC430 From firmware 4 0 182 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 262: ...Dimensions and weight 12 5 Mounting bracket FC430 From firmware 4 0 262 Operating Instructions 06 2017 A5E39789392 AA ...
Страница 534: ...Index FC430 From firmware 4 0 534 Operating Instructions 06 2017 A5E39789392 AA ...