Functions
2.15 Flexible Protection Functions
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
191
2.15.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
0
FLEXIBLE FUNC.
OFF
ON
Alarm Only
OFF
Flexible Function
0
OPERRAT. MODE
3-phase
1-phase
no reference
3-phase
Mode of Operation
0
MEAS. QUANTITY
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
df/dt rising
df/dt falling
Binary Input
Please select
Selection of Measured
Quantity
0
MEAS. METHOD
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental
Selection of Measurement
Method
0
PICKUP WITH
Exceeding
Dropping below
Exceeding
Pickup with
0
CURRENT
Ia
Ib
Ic
In
In sensitive
Ia
Current
0
VOLTAGE
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Please select
Voltage
0
POWER
Ia Va-n
Ib Vb-n
Ic Vc-n
Ia Va-n
Power
0
VOLTAGE SYSTEM
Phase-Phase
Phase-Ground
Phase-Phase
Voltage System
0
P.U. THRESHOLD
0.03 .. 40.00 A
2.00 A
Pickup Threshold